background image

Proline Promass 80

Commissioning

Hauser

21

5.4 Calling the Commissioning Quick Setup

All the functions needed for commissioning are called up automatically with the Quick Setup. 

The functions can be changed and adapted to the process in question.
1.

 

  Enter the function matrix (starting with measured value display)

2.

 

  Select the group QUICK SETUP

 

  Con

fi

rm selection

3.

QUICK SETUP COMMISSIONING function appears.

4.

Intermediate step if configuration is blocked:

 

  Enter the code 

80 

(confirm with 

) and thus enable configuration

5.

 

  Go to Commissioning Quick Setup

6.

 

  Select YES

 

  Con

fi

rm selection

7.

 

  Start Commissioning Quick Setup

8.

Configure the individual functions/settings:

– Via 

P

-key, select option or enter number

– Via 

F

-key, confirm entry and go to next function

– Via 

Q

-key, return to Setup Commissioning function 

(settings already made are retained)

Note! Observe the following when performing the Quick Setup:

• Configuration selection: Select the ACTUAL SETTING option

• Unit selection: This is not offered again for selection after configuring a unit

• Output selection: This is not offered again for selection after configuring an output

• Automatic configuration of the display: select YES

– Main line = Mass flow

– Additional line = Totalizer 1

• If asked whether additional Quick Setups should be executed: select NO

All the available functions of the measuring device and their configuration options as well as 

additional Quick Setups, if available, are described in detail in the "Description of Device 

Functions" Operating Instructions. The related Operating Instructions can be found on the 

CD-ROM.
The measuring device is ready for operation on completion of the Quick Setup.

Summary of Contents for Proline Promass 80

Page 1: ...e Operating Instructions provided in the scope of supply Detailed information about the measuring device is provided in the Operating Instructions and the additional documentation On the CD ROM supplied is not included in the delivery for all device versions Available for all measuring device versions via Internet www endress com deviceviewer Smartphone tablet Endress Hauser Operations App ...

Page 2: ... point 5 2 2 Installation conditions 5 2 3 Post installation 9 2 4 Post installation check 12 3 Wiring 13 3 1 Connecting the various housing types 14 3 2 Degree of protection 15 3 3 Post connection check 15 4 Hardware settings 16 4 1 Device address 16 5 Commissioning 18 5 1 Switching on the measuring device 18 5 2 Operation 19 5 3 Navigating within the function matrix 20 5 4 Calling the Commission...

Page 3: ...ns provide detailed information on the measuring device The measuring device may only be installed in a de energized state Repairs may only be performed if a genuine spare parts kit is available and this repair work is expressly permitted If performing welding work on the piping the welding unit may not be grounded by means of the measuring device 1 3 Operational safety The measuring device is des...

Page 4: ... instruments Measuring devices for use in systems that need to be monitored are labeled accordingly on the nameplate Relevant national regulations must be observed when using these devices The documentation on the CD ROM for pressure instruments in systems that need to be monitored is an integral part of the entire device documentation The installation regulations connection data and safety instru...

Page 5: ...ssociated Technical Information on the CD ROM 2 2 2 Mounting location The following mounting locations are recommended Upstream from assemblies such as valves T pieces elbows etc On the pressure side of pumps for high system pressure At the lowest point in an ascending pipe for high system pressure A0007408 To transport the unit use slings slung around the process connections or use lugs if availa...

Page 6: ... the bottom Promass A Recommended Possible m Possible m p Promass E Recommended Recommended n Recommended o p Promass F Recommended Recommended n Recommended o p Promass F HT Compact version Recommended Not suitable Recommended o p Promass F HT Remote version Recommended Possible n Recommended o p Promass H Recommended Recommended Recommended p Promass I Recommended Recommended Recommended p Proma...

Page 7: ... angle bracket Vertical We recommend two installation versions when mounting vertically Mounted directly on a wall using the base plate Measuring device supported on an angle bracket mounted on the wall A0018980 Horizontal We recommend the following installation version when mounting horizontally Measuring device standing on a firm support base A0018979 2 2 4 Heating For information on the heating...

Page 8: ...Installation Proline Promass 80 8 Endress Hauser 2 2 6 Inlet and outlet runs No inlet and outlet runs are required 2 2 7 Vibrations No measures are necessary ...

Page 9: ... the stop end of the thread c Turn the transmitter counterclockwise max 360 to the desired position d Retighten the setscrew c e f a b d 180 180 Nicht unter Spannung öffnen K e e p c o v er t i g h t w h i l e c i r c u i t s a r e a l i v e N e p a s o u v r i r l a p p a r e i l s o u s t e n s i o n K e e p c o v e r t i g h t w h i l e c i r c u i t s a r e a l i v e max 360 Nicht eigensichere...

Page 10: ...lay A0007541 a Press in the side latches on the display module and remove the module from the cover plate of the electronics compartment b Turn the display to the desired position max 4 45 in both directions and reset it onto the cover plate of the electronics compartment 4 45 a b ...

Page 11: ...wards Mounted directly on the wall Pipe mounting A0007542 1 Connection compartment 2 Securing screws M6 max ø 6 5 mm 0 25 screw head max ø 10 5 mm 0 4 3 Housing bores for securing screws A0007543 Caution Danger of overheating If the device is mounted on a warm pipe make sure that the housing temperature does not exceed 60 C 140 F which is the maximum temperature permitted 1 2 3 3 90 3 54 35 1 38 1...

Page 12: ... labeling correct visual inspection Correct internal diameter and correct surface roughness quality Has the correct sensor orientation been selected in terms of type fluid properties fluid temperature Does the arrow on the sensor point in the direction of the flow in the pipe Is the measuring device protected against moisture and sunlight Is the measuring device protected against overheating 245 9...

Page 13: ...of damaging the electronic components Only connect sensors and transmitters with the same serial number Observe the cable specifications of the connecting cable Operating Instructions on the CD ROM Note Install the connecting cable securely to prevent movement In addition for measuring devices with fieldbus communication Caution Risk of damaging the electronic components Observe the cable specific...

Page 14: ...ower supply cable Signal cable Fieldbus cable Connecting cable connection 5 Sensor transmitter connecting cable A0007547 Transmitter connection 1 2 3 4 Connection diagram inside the connection compartment cover Power supply cable Signal cable or fieldbus cable Optional Connecting cable connection 5 Sensor transmitter connecting cable A0008037 Transmitter connection 1 Connection diagram inside the ...

Page 15: ...ate strain relief and are they routed securely Is the cable type route completely isolated Without loops and crossovers Are all screw terminals correctly tightened Are all the cable entries installed correctly tightened and properly sealed Cable routed as a water trap in loops Are all housing covers installed and correctly tightened In addition for measuring devices with fieldbus communication Are...

Page 16: ...ches Warning Risk of electric shock Risk of damaging the electronic components All the safety instructions for the measuring device must be observed and all the warnings heeded 22 Use a workspace working environment and tools purposely designed for electrostatically sensitive devices A0007551 a Switch off the power supply before opening the device b Loosen the cheese head screw of the securing cla...

Page 17: ...hown 1 16 32 device address 49 b Miniature switches for the address mode method of addressing OFF factory setting software addressing via local operation operating program ON hardware addressing via miniature switches c Miniature switch not assigned 16 1 3 32 2 4 64 3 4 1 2 b OFF ON 1 1 2 2 4 3 8 4 a OFF ON c 16 1 3 32 2 4 64 3 4 1 2 b OFF ON 1 1 2 2 4 3 8 4 a OFF ON c DP PA ...

Page 18: ...power up checks and device self checks As this procedure progresses the following messages can appear on the onsite display The measuring device starts operating as soon as the startup procedure is complete Various measured values and or status variables appear on the display Note If an error occurs during startup this is indicated by an error message The error messages that occur most frequently ...

Page 19: ...cting 3 Enter key for calling the function matrix saving When the keys are pressed simultaneously Esc Exit the function matrix step by step 3 sec cancel data input and return to the measured value display A0007561 1 Type of error P Process error S System error 2 Error message type Fault message Notice message 3 Error number 4 Duration of the last error that occurred Hours Minutes Seconds 5 Error d...

Page 20: ...ct the group e g OPERATION F Confirm selection 3 N Select function e g LANGUAGE 4 P Enter code 80 only for the first time you access the function matrix F Confirm entry P Change function selection e g ENGLISH F Confirm selection 5 Q Return to measured value display step by step 6 Q 3 s Return immediately to measured value display Esc E 3s E Esc Esc m o n E E E E E E E p q q r ...

Page 21: ...key confirm entry and go to next function Via Q key return to Setup Commissioning function settings already made are retained Note Observe the following when performing the Quick Setup Configuration selection Select the ACTUAL SETTING option Unit selection This is not offered again for selection after configuring a unit Output selection This is not offered again for selection after configuring an ...

Page 22: ...he device address can be configured via Miniature switches see section Hardware settings 16 Local operation see description below Note The Commissioning Quick Setup has to be executed before setting the device address 1 F Enter the function matrix 2 P Select the COMMUNICATION group F Confirm selection 3 N Select the BUS ADDRESS function 4 P Enter the desired device address F Confirm entry 5 P 3 s ...

Page 23: ...current flow is outside the set range 1 Change the upper range or lower range values entered 2 Increase or reduce flow as applicable 701 Process error message P Notice message EXC CURR LIM 701 The maximum current value for the measuring tube exciter coils has been reached since certain fluid characteristics e g high gas or solid content are in the limit range The device continues to work correctly...

Page 24: ...age CURRENT SPAN n 351 to 354 Quality Code HEX measured value status 0x54 0x55 0x56 Quality status UNCERTAIN Quality substatus Engineering unit range violation Limits O K Low High Flow is out of range See HART table 701 Process error mess P Notice message EXC CURR LIM 701 Quality Code HEX measured value status 0x40 0x41 0x42 Quality status UNCERTAIN Quality substatus Non specific Limits O K Low Hi...

Page 25: ...Proline Promass 80 Commissioning Endress Hauser 25 ...

Page 26: ...Commissioning Proline Promass 80 26 Endress Hauser ...

Page 27: ...Proline Promass 80 Commissioning Endress Hauser 27 ...

Page 28: ...www addresses endress com ...

Reviews: