SmarTec S CLD 132 PROFIBUS-PA/-DP
Operation
28
EHauser
SmarTec S CLD 132 partial configuration using the manufacturer-specific
GSD file
Replacing measured variables with free places.
With this configuration, only the transfer of both of the transmitter’s measured values
(conductivity/ concentration) is activated. A free place must be inserted for the
temperature value, which are not required.
Note!
Maximum two AI blocks and one MRS can be configured from this GSD file. The AI
blocks are always assigned to the following measured variables:
AI 1 = Main measured value
AI 2 = Temperature
This guarantees that the measured variables agree with field devices from other
manufacturers.
Byte
length
(Input)
Byte
length
(Output)
Data blocks
Status
Access
GSD
Block description
GSD
Extended
block code
0 ... 4
–
Analog Input
block 1
(Main meas.
value)
active
read
Main Process Value
0x42, 0x84, 0x08,
0x05
–
–
Free place
inactive
–
Free Place
0x00
0 ... 1
MRS
active
write
MRS
0x82, 0x81, 0x05,
0x05