Picomag IO-Link
Commissioning
Hauser
23
Menu: "Guidance" → System units
Parameter overview with brief description
Parameter
Description
Selection
Factory setting
Volume flow unit
Select the unit for the volume flow.
• l/s, m³/h, l/min, l/h
• gal/min (us), fl. oz/min
l/min
Volume unit
Select the unit for the volume.
• ml, l, m³
• fl. oz (us), gal (us)
ml
Temperature unit
Select the unit for the temperature.
• °C
• °F
°C
Totalizer unit
Select the unit for the totalizer.
• ml, l, m³
• kl, Ml
• fl. oz (us), gal (us)
• kgal (us)
m³
Conductivity unit
Select the unit for conductivity.
• µS/cm
• S/m
• mS/cm
µS/cm
9.3.3
Setting the installation direction and measurement
The
Sensor
submenu contains parameters for specific settings of the measuring device.
Navigation
Menu: "Guidance" → Sensor
Parameter overview with brief description
Parameter
Description
Selection/input
Factory setting
Installation
direction
Select the installation
direction.
• Flow in arrow direction (forwards)
Positive flow measurement in the direction of the arrow.
• Flow against arrow direction (backwards)
Positive flow measurement in the opposite direction of the arrow.
Flow in arrow direction
(forwards)
On value
Enter the on value for
low flow cut off.
Positive floating point number
A flow measured value that is less than the value of the on value
forces the display to zero. In the event of plant downtime, this
prevents the totalizer from continuing to totalize even though
there is no flow.
The measured value flashes on the display when low flow cut off is
active.
Low flow cut off is deactivated again as soon as the flow measured
value exceeds 1.5 times the on value.
Depends on the nominal
diameter:
DN 15 (½"):
0.05 l/min (0.013 gal/min)
DN 20 (¾"):
0.1 l/min (0.026 gal/min)
DN 25 (1"):
0.2 l/min (0.052 gal/min)
DN 50 (2"):
1.5 l/min (0.4 gal/min)
Damping
Enter the time constant
for damping the flow
measured value.
0 to 10 s
0 s