Picomag IO-Link
Appendix
Hauser
55
Designation
ISDU
(hex)
ISDU
(dec)
Size
(byte)
Data type Access
Value range
Factory setting
Range
limits
Pulse output P-Out
Pulse Value
Unit selection list from
Unit
Volume
0x03E8
1000
4
float
r/w
0.5/1.0/2.0/10.0 ml
10¯⁹
9.9·10⁹
Switch output S-Out 1
Switch Polarity
0x032B
811
2
uint
r/w
PNP=0
NPN=1
PNP
Switch Function
0x0320
800
2
uint
r/w
alarm=0
off=1
on=2
lim.vol.flow=3,
lim.temp.=4
lim.vol.=5
lims=11
win.vol.flow=6
win.temp.=7
win.vol.=8
wins=13
epd=9
alarm
Q-ON-Value
Unit selection list from
Unit
Volumeflow
0x0321
801
4
float
r/w
20/40/80/600 l/min -9.9·10⁹
9.9·10⁹
Q-OFF-Value
Unit selection list from
Unit
Volumeflow
0x0322
802
4
float
r/w
15/30/60/450 l/min -9.9·10⁹
9.9·10⁹
T-ON-Value
Unit selection list from
Unit
Temperature
0x0327
807
4
float
r/w
+ 60 °C
-9.9·10⁹
9.9·10⁹
T-OFF-Value
Unit selection list from
Unit
Temperature
0x0328
808
4
float
r/w
+ 50 °C
-9.9·10⁹
9.9·10⁹
V-ON-Value
Unit selection list from
Unit
Totalizer
0x0329
809
4
float
r/w
0.2/0.4/0.8/6.0 m³
-9.9·10⁹
9.9·10⁹
V-OFF-Value
Unit selection list from
Unit
Totalizer
0x032A
810
4
float
r/w
0.15/0.3/0.6/4.5 m³
-9.9·10⁹
9.9·10⁹
s-ON-Value
Unit selection list from
Unit
Conductivity
0x0325
805
4
float
r/w
500
-9.9·10⁹
9.9·10⁹
s-OFF-Value
Unit selection list from
Unit
Conductivity
0x0326
806
4
float
r/w
200
-9.9·10⁹
9.9·10⁹
Voltage output U-Out 1
U - OUT Assign
0x02BC
700
2
uint
r/w
off=0
volume flow=1
temperature=2
conductivity=4
volume flow
Q-Start-Value
ASP
Unit selection list from
Unit
Volumeflow
0x02BD
701
4
float
r/w
0 l/min
Q-End-Value
AEP
Unit selection list from
Unit
Volumeflow
0x02BE
702
4
float
r/w
25/50/100/750
l/min