Commissioning
Micropilot M FMR244 with FOUNDATION Fieldbus
54
Hauser
The basic setup is sufficient for successful commissioning in most applications. Complex measuring
operations necessitate additional functions that the user can use to customise the Micropilot as
necessary to suit his specific requirements. The functions available to do this are described in detail
in the BA 221F.
Comply with the following instructions when configuring the functions in the "
basic setup
"
(00)
:
• Select the functions as described on Page 26.
• Some functions can only be used depending on the parameterisation of the instrument. For
example, the pipe diameter of a stilling well can only be entered if "
stilling well
" was selected
beforehand in the "
tank shape
"
(002)
function.
• Certain functions (e.g. starting an interference echo mapping (053)) prompt you to confirm your
data entries. Press
O
or
S
to select "
YES
" and press
F
to confirm. The function is now started.
• If you do not press a key during a configurable time period (
→
function group "
display
"
(09)
),
an automatic return is made to the home position (measured value display).
!
Note!
• The instrument continues to measure while data entry is in progress, i.e. the current measured
values are output via the signal outputs in the normal way.
• If the envelope curve mode is active on the display, the measured values are updated in a slower
cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has
been optimised.
• If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM.
"
Caution!
All functions are described in detail, as is the overview of the operating menu itself, in the manual
“
Description of the instrument functions
−
BA 221F
”, which is found on the enclosed CD-
ROM.
!
Note!
The default values of the parameters are typed in
boldface
.