Micropilot M FMR244 with FOUNDATION Fieldbus
Operation
Hauser
43
5.5.7
Diagnostic Block
Operation
The diagnostic block contains the error messages of the instrument. These parameters can also be
addressed by using the VU331 display module.
The diagnostic block is opened by clicking on the "diagnostic" line.
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. In order to resume operation, change
MODE_BLK to AUTO
1)
.
Block administration parameters
Methods
The FOUNDATION Fieldbus specification provides for the use of so-called methods to simplify the
operation of the device. A method is an interactive sequence of steps that must be followed in order
to obtain a particular function from the device.
The Micropilot M has got the following methods:
• Set to customer default
• Diagnostics
Most of these methods are identical to the respective function group in the operating menu. A
detailed description of them can be found in the "Description of Instrument functions", BA221F/
00/en.
Instrument specific parameters
1)
If MODE_BLK refuses to be changed to AUTO, an error is present. Control all parameters, perform the required changes and try again to change MODE_BLK
to AUTO.
Parameter
Description
MODE_BLK
See description in Resource block. The possible operating modes of the Sensor block are:
– AUTO: the block is operating as normal.
– OOS: the block is out of service.
TAG_DESC
User description of the intended application of the block.
BLOCK_ERROR
Shows the error status associated with the block components
– Out-of-Service: the block is in OOS mode.
Parameter
Position
Indicator
rel.
Index
Variable Name
Size
[bytes]
Type
Access
Storage
Class
Changeable
in Mode
present error
0A0
13
PARACTUALERROR
2
Unsigned16
RO
dynamic
Auto, OOS
previous error
0A1
14
PARLASTERROR
2
Unsigned16
RO
non-vol.
Auto, OOS
clear last error
0A2
15
PARCLEARLASTERROR
1
Unsigned8
RW
dynamic
Auto, OOS
reset
0A3
16
PARRESET
2
Unsigned16
RW
dynamic
OOS
unlock parameter
0A4
17
PAROPERATIONCODE
2
Unsigned16
RW
non-vol.
OOS
psw-no.
0C2
18
PARPROTSOFTVERSIONSTRING
16
VisibleString
RO
const
Auto, OOS