Micropilot FMR66B HART
Hauser
V. 1, Rev. 2, 26-07-2022
9
HART specification:
7
DD version:
1
Device description files (DTM, DD)
Information and files under:
•
www.endress.com
On the product page for the device: Documents/Software → Device drivers
•
www.fieldcommgroup.org
HART load:
Min. 250 Ω
HART device variables
The following measured values are assigned to the device variables at the factory:
Device variable
Measured value
Assign PV
Level linearized
Assign SV
Distance
Assign TV
Absolute echo amplitude
Assign QV
Relative echo amplitude
1)
The PV is always applied to the current output.
Choice of HART device variables
• Level linearized
• Distance
• Terminal voltage
• Electronics temperature
• Sensor temperature
• Absolute echo amplitude
• Relative echo amplitude
• Area of incoupling
• Build-up index
• Build-up detected
• Foam index
• Foam detected
• Percent of range
• Loop current
• Terminal current
• Not used
Supported functions
• Burst mode
• Additional transmitter status
• Device locking
Wireless HART data
Minimum start-up voltage:
10.5 V
Start-up current:
< 3.6 mA
Starting time:
< 15 s
Minimum operating voltage:
10.5 V
Multidrop current:
4 mA
Time to establish connection:
< 30 s