Installation
25
3.2.2
Panel mounting, Installation dimensions
Fig. 2:
Panel mounting and installation dimensions. All dimensions in mm or (inch)
• Installation depth without terminal cover: approx. 158 mm (6.22") (incl. terminals and fastening
clips)
• Installation depth with terminal cover: approx. 197 mm (7,76")
• Panel cutout: 138
+1
x 138
+1
mm (5.43
+0.04
x 5.43
+0.04
")
• Panel thickness: 2 to 40 mm (0.08 to 1.58")
• Max. viewing angle range: from the display central axis 50° in all directions
• Securing to DIN 43 834
1.
Push the unit through the panel cutout from the front. To avoid heat accumulation, we
recommend keeping a distance of > 15 mm (>0.59 inch) from the walls and other units.
2.
Hold the unit horizontally and then hang the two jack screws in the openings opposite (either
on left or right housing side, or at top or bottom).
3.
Tighten the screws on the jack screws equally with a screwdriver such that a secure seal to the
control panel is guaranteed (dynamometric screwdriver: 100 Ncm).
!
Note!
• A distance of min. 7 mm (0.28 inch) between the devices has to be observed if aligning the
devices in the Y-direction (vertically above one another).
195.2
(7.69)
149.2
(5.87)
Y
X
138
(5.43
)
+1
+0.04
7
(0.28)
138 (5.43)
196.2 (7.72)
58.2 (2.29)
138
(5.43)
156.2
(6.15)
18.2
(0.72)
157.8 (6.21)
141 (5.55)
105.5
(4.15)
23.3 (0.92)
35.1
(1.38)
138
(5.43)
5
(0.2)
192 (7.56)
Summary of Contents for Memograph M
Page 3: ...3 ...
Page 19: ...Inbetriebnahme und Bedienung 19 ...
Page 21: ...21 ...
Page 37: ...Commissioning and operation 37 ...
Page 39: ...39 ...
Page 55: ...Mise en service et utilisation 55 ...
Page 57: ...57 ...
Page 73: ...Messa in servizio e funzionamento 73 ...
Page 74: ......
Page 75: ......
Page 76: ...www endress com worldwide KA248R 09 c4 05 10 71035349 FM SGML6 0 ProMoDo ...