Wiring
30
4.2
Terminal assignment
"
Caution!
If high-energy transients occur when using long signal cables, we recommend connecting a suitable
overvoltage protection (e.g. E+H HAW560/562).
Use shielded signal lines for serial interfaces!
4.2.1
Cable specification, spring terminals
All connections on the rear of the unit are designed as screw or spring terminal blocks with reverse
polarity protection. This makes the connection very quick and easy. The spring terminals are
actuated with a slotted screwdriver (size 0).
Please note the following when connecting:
• Wire cross-section, digital I/O, RS485 and analog inputs: max. 1.5 mm
2
(14 AWG) (spring
terminals)
• Wire cross-section, power supply: max. 2.5 mm
2
(13 AWG) (screw terminals)
• Wire cross-section, relays: max. 2.5 mm
2
(13 AWG) (spring terminals)
• Stripped length: 10 mm (0.39 inch), 6 mm (0.24 inch) for power terminal
!
Note!
No ferrules have to be used when connecting flexible wires to spring terminals.
4.2.2
Connecting the interfaces
Ethernet, RS232/RS485 and USB connection
Details on connecting the interfaces can be found in the Operating Instructions on CD-ROM, chap-
ter 4.2.
4.3
Degree of protection
At the front, the unit meets the requirements of ingress protection IP65.
Summary of Contents for Memograph M
Page 3: ...3 ...
Page 19: ...Inbetriebnahme und Bedienung 19 ...
Page 21: ...21 ...
Page 37: ...Commissioning and operation 37 ...
Page 39: ...39 ...
Page 55: ...Mise en service et utilisation 55 ...
Page 57: ...57 ...
Page 73: ...Messa in servizio e funzionamento 73 ...
Page 74: ......
Page 75: ......
Page 76: ...www endress com worldwide KA248R 09 c4 05 10 71035349 FM SGML6 0 ProMoDo ...