Flow diagram of function test
1) lit: fault in sensor
2) lit: fault in data transfer
3) lit: fault in Nivotester
4) flashing: permanent self-monitoring
5) lit: level below maximum
6) lit: level alarm
7) "test" key
8) lit: fault; unlit: normal operation
!
Note!
If one of the test criteria from the test sequences described above is not fulfilled, the device may no longer be
used as part of a safety instrumented system.
The purpose of proof-testing is to detect random device failures. The impact of systematic errors on the safety
function is not covered by this test and must be assessed separately.
Systematic errors can be caused, for example, by process material properties, operating conditions, buildup or
corrosion.
z 26
d 26
b 28
d 18
b 20
d 18
b 20
FTL670
s
z 26
d 26
b 28
s
*
*
0
1
2
3
4
5
6
7
8
1)
6)
2)
5)
3)
8)
7)
4)
yellow
yellow
yellow
yellow
green
red
red
Test key pressed
Level alarm relay de-energised
Fault alarm relay de-energised
energised
Time
energised
Test key released
Summary of Contents for Liquiphant S FDL60
Page 3: ...Liquiphant S Nivotester Endress Hauser 3 SIL Declaration of Conformity SIL 03013b ...
Page 17: ...Liquiphant S Nivotester Endress Hauser 17 ManagementSummary ManagementSummary ...
Page 18: ...Liquiphant S Nivotester 18 Endress Hauser ManagementSummary ManagementSummary ...
Page 19: ...Liquiphant S Nivotester Endress Hauser 19 ManagementSummary ManagementSummary ...
Page 20: ...Liquiphant S Nivotester 20 Endress Hauser Certificate TUEV_Z10 03 11 20351 002 en ...
Page 21: ...Liquiphant S Nivotester Endress Hauser 21 ...
Page 22: ...Liquiphant S Nivotester 22 Endress Hauser ...