Liquiphant S, Nivotester
Hauser
5
In addition to the fail-safe contact, the fault-signalling contact (alarm relay) works as a changeover contact and
goes to idle condition when:
• One of the following faults occurs:
– Fault in the sensor FDL60, FDL61 (e.g. corrosion, electronics fault)
– Fault in data transfer
– Fault in FTL670 limit switch
• The mains voltage fails
!
Note!
When the alarm relay changes to idle condition, the fail-safe contact also opens.
!
Note!
Correct installation is essential to the safe operation of the device.
The instructions on installation conditions in the Operating Instructions (
6, "Supplementary device
documentation") must be followed.
Permitted device types
The functional safety assessment described in this manual applies to the device versions listed below.
Unless otherwise indicated, all subsequent versions can also be used for safety functions.
In the event of device modifications, a modification process compliant with IEC 61508 is applied.
Device versions valid for use in safety-related applications:
Nivotester FTL670
The device version is suitable for use in safety-related applications.
Liquiphant S FDL60
Options
Designation
Version
010
Approval
all
020
Process Connection
all
025
Fork Surface Finish
all
040
Electronics; Output
all
050
Housing; Cable Entry
all
Liquiphant S FDL61
Options
Designation
Version
010
Approval
all
020
Process Connection
all
025
Fork Surface Finish
all
030
Probe Length
all
040
Electronics; Output
all
050
Housing; Cable Entry
all
Summary of Contents for Liquiphant S FDL60
Page 3: ...Liquiphant S Nivotester Endress Hauser 3 SIL Declaration of Conformity SIL 03013b ...
Page 17: ...Liquiphant S Nivotester Endress Hauser 17 ManagementSummary ManagementSummary ...
Page 18: ...Liquiphant S Nivotester 18 Endress Hauser ManagementSummary ManagementSummary ...
Page 19: ...Liquiphant S Nivotester Endress Hauser 19 ManagementSummary ManagementSummary ...
Page 20: ...Liquiphant S Nivotester 20 Endress Hauser Certificate TUEV_Z10 03 11 20351 002 en ...
Page 21: ...Liquiphant S Nivotester Endress Hauser 21 ...
Page 22: ...Liquiphant S Nivotester 22 Endress Hauser ...