Levelflex FMP55 HART
Storage, Transport
Hauser
19
5
Storage, Transport
5.1
Storage conditions
• Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use the original packaging.
5.2
Transport product to the measuring point
L
WARNING
Housing or probe may be damaged or break away.
Risk of injury!
‣
Transport the measuring device to the measuring point in its original packaging or at
the process connection.
‣
Do not fasten lifting devices (hoisting slings, lifting eyes etc.) at the housing or the
probe but at the process connection. Take into account the mass center of the device in
order to avoid unintended tilting.
‣
Comply with the safety instructions, transport conditions for devices over 18kg
(39.6lbs) (IEC61010).
A0013920
NOTICE
Shipping lock for FMP5x with coax probe
‣
For FMP5x with coax probe the coax tube is not fixed permanently to the electronics
housing. For shipping and transport it is secured with two cable ties. In order to prevent
the spacer at the probe rod from moving along the probe, these cable ties must not be
loosened when transporting and mounting the device. They may only be undone
directly before screwing the device flange to the process connection.