Operating menu
Levelflex FMP55 HART
112
Hauser
Selection
SI units
• mm
• m
US units
• ft
• in
Factory setting
m
Tank type
Navigation
Setup → Tank type
Prerequisite
Medium type
=
Liquid
Description
Select tank type.
Selection
• Metallic
• Bypass / pipe
• Non metallic
• Mounted outside
• Coaxial
Factory setting
Depending on the probe
Additional information
• Depending on the probe some of the options mentioned above may not be available or
there may be additional options.
• For coax probes, the default setting is
Tank type = Coaxial
and can not be changed.
• For probes with metallic center washer,
Tank type = Bypass / pipe
is preset and can not
be changed.
Tube diameter
Navigation
Setup → Tube diameter
Prerequisite
•
=
Bypass / pipe
• The probe is coated.
Description
Specify diameter of bypass or stilling well.
User entry
0 to 9.999 m
Factory setting
0.0384 m