Levelflex FMP55 HART
Operating menu
Hauser
153
Additional information
Meaning of the options
•
Min.
The current output adopts the value of the lower alarm level according to the
Current
span
•
Max.
The current output adopts the value of the upper alarm level according to the
Current
span
•
Last valid value
The current remains constant at the last value it hat before the error occurred.
•
Actual value
The output current follows the actual measured value; the error is ignored.
•
Defined value
The output current assumes the value defined in the
Failure current
parameter
The error behavior of other output channels is not influenced by these settings but is
defined in separate parameters.
Failure current
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Failure current
Prerequisite
Failure mode (→ 152)
Defined value
Description
Enter current output value in alarm condition.
User entry
3.59 to 22.5 mA
Factory setting
22.5 mA
Output current 1 to 2
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Output curr. 1 to 2
Description
Displays calculated output current.