Commissioning
Proline t-mass I 300 HART
120
Hauser
9.6.1
Function scope of the "Configuration management" parameter
Options
Description
Cancel
No action is executed and the user exits the parameter.
Execute backup
A backup copy of the current device configuration is saved from the HistoROM
backup to the memory of the device. The backup copy includes the transmitter data
of the device.
Restore
The last backup copy of the device configuration is restored from the device
memory to the device's HistoROM backup. The backup copy includes the
transmitter data of the device.
Compare
The device configuration saved in the device memory is compared with the current
device configuration of the HistoROM backup.
Clear backup data
The backup copy of the device configuration is deleted from the memory of the
device.
HistoROM backup
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.
9.7
Simulation
The
Simulation
submenu enables you to simulate, without a real flow situation, various
process variables in the process and the device alarm mode and to verify downstream
signal chains (switching valves or closed-control loops).
Navigation
"Diagnostics" menu → Simulation
‣
Simulation
Assign simulation process variable
Process variable value
Current input 1 to n simulation
Value current input 1 to n
Status input simulation 1 to n
Input signal level 1 to n
Current output 1 to n simulation
Value current output 1 to n
Frequency output simulation 1 to n
Frequency value 1 to n
Summary of Contents for HART Proline t-mass I 300
Page 201: ......