Commissioning
Proline Promass 80
46
Hauser
!
Note!
• The display returns to the cell SETUP COMMISSIONING (1002) if you press the
Q
key combination during
parameter interrogation The stored parameters remain valid.
• The "Commissioning" Quick Setup must be carried out before one of the Quick Setups explained below is run.
m
Selecting DELIVERY SETTINGS returns each selected unit to the factory setting.
Selecting ACTUAL SETTINGS applies the units you have set previously.
n
Only units not yet configured in the current Setup are offered for selection in each cycle. The unit for mass, volume
and corrected volume is derived from the corresponding flow unit.
o
The YES option remains visible until all the units have been configured. NO is the only option displayed when no
further units are available.
p
Only the outputs not yet configured in the current Setup are offered for selection in each cycle.
q
The YES option remains visible until all the outputs have been configured. NO is the only option displayed when
no further outputs are available.
r
The "automatic parameterization of the display" option contains the following basic settings/factory settings:
YES: line 1= mass flow; line 2 = totalizer 1;
information line = operating/system conditions
NO: The existing (selected) settings remain.