Cerabar PMP71B HART
Commissioning
Hauser
39
9
Commissioning
9.1
Preparatory steps
The measuring range and the unit in which the measured value is transmitted correspond
to the data on the nameplate.
L
WARNING
The settings of the current output are relevant for safety!
This can result in product overflow.
‣
The setting for the current output depends on the setting in the
Assign PV
parameter.
‣
After changing the setting for the current output, check the setting for the span (LRV
and URV) and readjust it if necessary!
L
WARNING
Process pressure above or below permitted maximum/minimum!
Risk of injury if parts burst! Warning messages are generated if pressure is too high.
‣
If a pressure smaller than the minimum permitted pressure or greater than the
maximum permitted pressure is present at the device, a message is output.
‣
Use the device only within the sensor range limits!
9.1.1
As-delivered state
If no customized settings were ordered:
•
Assign PV
parameter
Pressure
option
• Calibration values defined by defined sensor nominal value
• The alarm current is set to min. (3.6 mA), (only if no other option was selected when
ordering)
• DIP switch to Off position
• Bluetooth switched on
9.2
Function check
Perform a function check before putting the measuring point into operation:
• "Post-installation check" checklist (see the "Installation" section)
• "Post-connection check" checklist (see the "Electrical connection" section)
9.3
Switching on the measuring device
All configuration tools offer a commissioning wizard that helps the user to configure
the most important configuration parameters (
Guidance
menu
Commissioning
wizard).