Electrical connection
Cerabar PMP71B HART
32
Hauser
NOTICE
Plug M12 and plug HAN7D: incorrect mounting can invalidate the IP protection class!
‣
The degree of protection only applies if the connecting cable used is plugged in and
screwed tight.
‣
The degree of protection only applies if the connecting cable used is specified according
to IP67, NEMA Type 4X.
‣
The IP protection classes are only maintained if the dummy cap is used or the cable is
connected.
6.4
Post-connection check
After wiring the device, carry out the following checks:
Is the potential matching line connected?
Is the terminal assignment correct?
Are the cable glands and dummy plugs leak-tight?
Are the fieldbus connectors properly secured?
Are the covers screwed down correctly?