DTM for Fieldgate SFG500
Fieldgate SFG500
28
Hauser
5
DTM for Fieldgate SFG500
This chapter contains a short description of the functions obtainable via the Fieldgate
SFG500 Device DTM. All functions are called by right-clicking on a connected DTM and
selecting the appropriate context menu. This procedure is not illustrated by screenshots.
5.1
Configuration
5.1.1
Fieldgate SFG500 CommDTM
NOTE!
• The identification parameters can be changed only when Fieldgate SFG500 is offline
The configuration menu opens the Fieldgate SFG500 CommDTM.
1. Right-click on the SFG500 node and select
Configuration
– The SFG500 Device DTM opens:
2. The parameters have the following significance:
Parameter
Meaning
Identification
If the SFG500 Device DTM is added manually to a network, the drop down menu allows
three ways of identifying the device to which the DTM is to be connected.
• Serial Number: The Serial Number entry box is enabled.
– Enter the serial number of the associated device and press
Enter
– The connection is made and the IP address and Device Tag are displayed
• IP Address: The IP Address entry box is enabled
– Enter the IP address of the associated device and press
Enter
– The connection is made and the serial number and Device Tag are displayed
• Device Tag: The Device Tag entry box is enabled
– Enter the device tag of the associated device and press
Enter
– The connection is made and the serial number and IP address are displayed
Serial Number
Displays the serial number of the connected device
• When offline, the box can also be used to reconnect to a different device, see above
IP Address
Displays the IP address of the connected device
• When offline, the box can also be used to reconnect to a different device, see above
Device Tag
Displays the Device Tag of the connected device.
• When offline, the box can also be used to reconnect to a different device, see above
• When online, the box can be used to change the tag of the connected device
Start Address
PROFIBUS address from which Fieldgate SFG500 starts scanning for devices on the bus
– Default value = 0
End Address
PROFIBUS address at which Fieldgate SFG500 stops scanning for devices on the bus
– Default value = 126