6.2.5
Change the block target mode
In general, the parameters of a FOUNDATION fieldbus transducer block can only be changed when
the block is out of service (OOS). Depending on how you have chosen to generate your parameter
list, this can be done from the live list, the block list or the parameter list. After all parameters have
been changed and downloaded, the block target mode must be set to Auto again.
1 All blocks in the selected device can be put out of service by putting the resource block out of
service in the live list
–
From the live list tap and hold on the resource block and select
Set Target Mode
from the context menu
–
Alternatively, from the block list tap on
OOS
in the block mode header
2 In the page which appears:
–
Remove the tick from Auto and tick
OOS
–
Tap on
OK
in the top righthand corner to execute the change
3 An individual block can be put out of service in the same manner as above by selecting the
block in the live list
–
Tap and hold on the block and select
Set Target Mode
from the context menu or
from the block list tap on
OOS
in the block mode header
–
In the page which appears, see Step 2, remove the tick from Auto and tick
OOS
–
Tap on
OK
in the top righthand corner to execute the change