EngyVolt RV15
Commissioning
21
First level
Second level
Third level
Addr (device address)
Choose value from between 1 to 247
RLY (relay)
OP1 (value assignment to pulse output
relay 1)
OP2 (value assignment to pulse output
relay 2)
Choose from:
• NONE
• kWh
• kvarh
RATE (pulse value)
Specifies the pulse value of
both
pulse
outputs.
Choose from:
• 0.1
• 1
• 10
• 100
• 1
000
PULS (pulse length)
Specifies the pulse length of
both
pulse
outputs.
Choose from:
• 60 ms
• 100 ms
• 200 ms
NRGY (energy)
Choose from:
• KILO
• MEGA
TEST
Choose from:
• disp ON (tests the segments of the
LC display)
• disp TOGL (display toggle. Tests the
segments of the LC display
alternately)
• PHAS SEQ (checks the phase
sequence)
SOFT (software)
Displays the version number of the
internal software (firmware)
6.2.1
Configuration example for the current transformer primary value
1.
A0016388
Press the and keys simultaneously and hold for 5 seconds.
Ã
A0016389
The screen to enter the password is displayed.
2. To enter the default password "0000" which is set at the factory, press the key four times
or enter a password that has already been configured and press to confirm.
Ã
A0016390
The screen to make the settings for the system configuration is displayed.
3. Repeatedly press the key until the screen to set the current transformer primary value "CT"
is displayed.