Wiring
4.1
Connection of the sensors
Connect the sensors CLS21D and CLS50 directly at the transmitter.
Connect the sensor CLS21 with the special measuring cable (included in the scope of delivery) at
the terminals in the assembly head.
Connection of the sensor CLS21:
1.
Unscrew the cover (pos. 1) from the assembly head (pos. 3).
2.
Push the measuring cable from the bottom through the assembly pipe.
3.
Connect the measuring cable according to
Fig. 18 to the terminals (pos. 2) inside the
assembly head.
4.
Push the plug (pos. 4) of the measuring cable onto the sensor head (pos. 5).
5.
Screw the sensor holder (pos. 6) into the bayonet lock of the assembly pipe.
6.
Mount a cable gland Pg 13.5 at the cover of the assembly head.
7.
Lead the measuring cable CYK71 through the cable gland.
8.
Connect the measuring cable CYK71 according to
Fig. 18 to the terminals (pos. 2).
9.
Screw the cover onto the assembly head.
a0007456
Fig. 17:
Connection of the measuring cable for CLS21
1
2
3
4
5
6
Assembly head cover
Terminals
Assembly head
Plug of the measuring cable
Sensor CLS21
Sensor holder
1
2
3
4
5
6