Deltabar FMD72
Diagnostics and troubleshooting
65
Diagnostics event
Cause
Corrective measure
Code
Description
S945
Pressure limit LP
• The configured overpressure or underpressure limit of
sensor module LP is exceeded.
• Sensor module LP defective.
• Check the pressure
value
• Change pressure limit
value
• Contact Endress
+Hauser Service
S971
Adjustment
• The current is outside the permitted range from 3.8 to
20.5 mA.
• The present pressure value is outside the configured
measuring range (but within the sensor module range,
if applicable).
• Check the pressure
value
• Check the measuring
range
• Check the setting
12.3
Response of output to errors
The behavior of the current output in case of fault is defined by the following parameters:
12.4
Firmware version
Date
Firmwar
e version
Modifications
Documentation
CD-ROM
Operating Instructions
Description of Device
Parameters
Technical Information
01.2012 01.00.00
Original Firmware
Can be operated using
FieldCare from version
2.08.00
CD00520P/00/A2/01.12 BA01044P/00/EN/01.12 GP01013P/00/EN/01.12 TI01033P/00/EN/01.12
CD00520P/00/A2/02.12 BA01044P/00/EN/02.12 GP01013P/00/EN/02.12 TI01033P/00/EN/02.12
12.5
Disposal
When disposing, separate and recycle the device components based on the materials.
Summary of Contents for Deltabar FMD72
Page 2: ......
Page 107: ......
Page 108: ...www endress com worldwide 71191239 71191239 BA01044P 00 EN 02 12 71191239 CCS COSIMA...