Deltabar FMD72
Description of device parameters
99
Tank description (173)
Navigation
Setup
®
Advanced Setup
®
Linearization
®
Tank description (173)
Write permission
Operators/Service engineers/Expert
Description
Enter the tank description (max. 32 alphanumeric characters)
High Press. Side (183)
Navigation
Setup
®
High Press. Side (183)
Write permission
Operators/Service engineers/Expert
Description
Define which sensor module corresponds to the high-pressure side.
Options
• Sensor HP
• Sensor LP
Factory setting
Sensor HP
Output fail mode (051)/(190)
Navigation
Setup
®
Advanced Setup
®
Current output
®
Output fail mode (051)/(190)
Write permission
Operators/Service engineers/Expert
Description
Select Output fail mode. In case of an alarm, the current and the bargraph assume the current value
specified with this parameter.
Options
• Max: can be set from 21 to 23 mA
• Hold: last measured value is held.
• Min: 3.6 mA
Factory setting
Max (22 mA)
Cust. tag number (254)
Navigation
Diagnosis
®
Instrument info
®
Cust. tag number (254)
Write permission
Operators/Service engineers/Expert