Description of device parameters
Deltabar FMD72
88
Factory setting
Current point
Tank content (043)
Navigation
Setup
®
Advanced Setup
®
Linearization
®
Tank Content (043)
Diagnosis
®
Measured values
®
Tank Content (043)
Write permission
Operators/Service engineers/Expert
Description
Displays the level value after linearization.
Alarm Behav. P (050)
Navigation
Setup
®
Advanced Setup
®
Current output
®
Alarm Behav. P (050)
Write permission
Operators/Service engineers/Expert
Description
Set current output if sensor module limits are overshot or undershot.
Options
• Warning
The device continues to measure. An error message is displayed.
• Alarm
The output signal assumes a value that can be defined by the "Output fail mode (190)/(051)"
function.
• Special
– The lower sensor module limit is undershot (sensor module LP or HP or complete system):
Current output = 3.6 mA
– The upper sensor module limit is overshot (sensor module LP or HP or complete system):
Current output assumes a value of 21 - 23 mA, depending on the setting of the "High Alarm
Curr." parameter (052).
Factory setting
Warning
High Alarm Curr. (052)
Navigation
Setup
®
Advanced Setup
®
Current Output
®
High Alarm Curr. (052)
Write permission
Operators/Service engineers/Expert
Description
Enter the current value for maximum alarm current. See also "Output fail mode".
Input range
21 to 23 mA
Factory setting
22 mA