Ceraphant T PTC31, PTP31, PTP35
Accessories
Hauser
21
6.1.1
Adapter change
The adapter can be changed on PTP31 and PTP35.
P01-PTx3xxxx-17-xx-xx-xx-001
Fig. 14: Changing the adapter
➀
Sensor module with adapter thread
➁
Standard O-ring
➂
Adapter
Please note the following when changing the adapter:
• Use a new O-ring. Diameter 15.54 (0.61 in) x 2.62 mm (0.1 in).
With either EPDM 70 Shore FDA or FKM 70 Shore material.
• The device (sensor module) can be fixed in place with an open-ended wrench AF 27mm.
• The adapter can be screwed on with an open-ended wrench AF 28mm or AF 32mm
(depending on the process connection).
The maximum torque is 80Nm. The thread can become loose if exposed to severe strain
through pressure and temperature. For this reason, the air-tightness must be checked
regularly and the thread tightened if necessary. We recommend using Teflon tape as an
additional thread seal.
• When changing the adapter, make sure that the measuring diaphragm of the sensor is not
damaged.
!
Note! O-ring change
We recommend to change the O-ring in the same time frame as of all other sealings in your
process.
PTP 31
PTP 35
1
1
2
2
3
3