6.8

 

Adjust Temperature Compensation Slope 

The rectifier assumes that the battery temperature is 25°C when the Temperature 

Compensation Probe is not connected. Disconnect the Temperature Compensation 

Probe, and adjust the boost and float charge voltages to that required for 25°C. 

Reconnect the Temperature Compensation Probe and cool the metal lug to 0°C (using a 

container containing ice and water - do not immerse the probe in the water as it is not 

waterproof).  
Adjust the Temperature Compensation Slope to set the required charging voltage at this 

temperature as determined by the manufacturer’s specification. 

6.9

 

Adjusting the alarm output volt low/high setting 

The High Volts and Low Volts Alarm Thresholds can be adjusted to suit the application. 

This adjustment requires a variable voltage power supply (that has a maximum voltage 

exceeding the over-voltage value to be set). 
Connect the variable voltage power supply across the load connections of the rectifier 

(check that +ve output of the variable supply is connected to the +ve load connection). 

Disconnect the Temperature Compensation Probe. Connect an accurate voltmeter across 

the output. Turn the mains on to the rectifier and adjust the variable voltage power 

supply up until the alarm activates. Adjust the ‘Alarm Output High’ trimpot to set the 

alarm limits. Use the same procedure to adjust the ‘Alarm Output Low ‘ limits. Se

Figure 

6: Alarm Configuration

 for details. 

Appendix I

 

E

NATEL 

E

NERGY 

S

TANDARD 

L

IMITED 

W

ARRANTY 

P

OLICY

 

Enatel warrants that its products shall be free from defects of material or workmanship 

under use consistent with correct installation and commission, normal operation, product 

specifications, Enatel’s written instructions, and regional standards compliance, for a 

period of one (1) year from the start date. The start date shall be defined as (a) the date 

the product is shipped from Enatel’s factory; or (b) in the case of resale by an authorized 

Enatel reseller, whichever is the lesser of i) the date on the sales invoice or ii) ninety (90) 

days after original shipment by Enatel factory. 
The warranty provides for repairing or replacing, at Enatel’s sole discretion, those 

products deemed defective by Enatel after inspection of its products returned by the 

customer to the factory or other Enatel authorized location within the warranty period. 

Replaced product provided by Enatel under the terms of this warranty does not extend 

the original warranty, replacement product assumes the warranty of the original product. 

Repaired product or component thereof has a warranty period of ninety (90) days or the 

remainder of the unexpired term of the original product warranty, whichever is greater. 

Summary of Contents for RW312U

Page 1: ...Installation and Operation Manual Model RW312U RW324U RW348U RW512U RW517U RW624U RW748U Series Rectifiers Version 3 6 Enatel DC System Manual...

Page 2: ...andard Limited Warranty Policy on page 22 System Compliance Low Voltage Directive LVD 2014 35 EU Electromagnetic Compatibility Directive EMC 2014 30 EU Copyright Enatel 2020 All rights reserved Releas...

Page 3: ...e Shutdown 8 2 11 Reverse Polarity Protection 8 2 12 Parallel Rectifier Operation 8 2 13 External Shutdown 9 2 14 Alarm Control Interface 9 2 15 Internal Alarm Card Optional 9 3 Installation 10 3 1 Ge...

Page 4: ...atel Energy Standard Limited Warranty Policy 22 I A Warranty Exclusions and Restrictions 23 I B Battery Warranty 23 I C Initiating a Warranty Claim 23 I D Disclaimer 24 I E Remark 24 TABLE OF FIGURES...

Page 5: ...10 240V 4A 12V 13 7V 11 5 15V 20A 300W RW324U 110 240V 4A 24V 27 4V 22 30V 10A 300W RW348U 110 240V 4A 48V 54 0V 45 60V 6A 300W RW512U 110 240V 8 5A 12V 13 7V 11 5 15V 35A 500W RW517U 110 240V 8 5A 17...

Page 6: ...nsation Probe is connected and the rectifier fails the LED may not show The monitor external signals are still correct To verify the condition unplug the Temperature Compensation Probe 2 2 Display A r...

Page 7: ...ttery ve supply the ve is common with the battery Do not connect the Battery and Load ve together The LVD voltage and the LVD Hysteresis voltage are pre set in the factory but may be adjusted to suit...

Page 8: ...the rectifier may shut down until the allowed voltage is restored 2 9 Input Inrush Current Limiter On start up the peak mains inrush current is limited to twice the maximum operating current The outpu...

Page 9: ...n allows remote monitoring of the rectifier The monitor connection is a RJ45 socket The pinout of the socket is as follows Table 3 Pin descriptions Pin Description Pin 1 Load Share signal 0 5V externa...

Page 10: ...he rectifier To isolate the rectifier from the mains power unplug the IEC mains connector from the rectifier DANGER Do not operate the rectifier if the covers are damaged or removed in any way WARNING...

Page 11: ...a minimum It is better to have a long mains lead and short low voltage cables The rectifier must be positioned so that airflow through the rectifier is not impeded in any way These rectifiers are conv...

Page 12: ...battery and the rectifier to protect the rectifier load and battery The fuse should be mounted close to the battery and have a high rupture current capability just above the rectifier capability This...

Page 13: ...ter if the cable is longer than necessary unlike the current carrying load and battery cables Caution Do not reverse the polarity of the cables from the battery This will blow an internal protection f...

Page 14: ...parallel using an RJ45 cable to connect between the alarm and control interface the alarm outputs on the Alarm Card give the status of all the connected units This means that you only need one alarm c...

Page 15: ...larm outputs share a Common contact 3 8 Rectifier Fail Mains Fail The Mains Fail Alarm is activated while the mains power is not present The Rectifier Fail Alarm can be configured to activate when the...

Page 16: ...on of the current from the rectifier 5 Disconnect the mains then double check the polarity of the cables to the load and then plug them into the rectifier Re connect the mains 6 If there is more than...

Page 17: ...t delivered by the rectifier is as expected Load Checks Connect battery but disconnect the main load to rectifier Connect a current meter in series with the battery Verify the current drawn by the bat...

Page 18: ...slow blow 6 SETTING CHANGES All setting changes must be carried out by suitably qualified personnel The rectifier is supplied from the factory with default parameters for normal operation These settin...

Page 19: ...Enatel DC System Manual Page 19 of 26 Model RWxxx Version 3 6 Figure 7 Trimpot Access Figure 8 Trimpot Functions Trimpot Access on product REAR See Figure 8 Trimpot Functions L R L R...

Page 20: ...ely 10 seconds for the rectifier to switch back to Float Charge mode Check that the rectifier is in Float Charge mode as indicated on the LEDs Adjust the Float Voltage trimpot to set the required floa...

Page 21: ...ge power supply across the load connections of the rectifier ensure that ve output of the variable supply is connected to the ve load connection Disconnect the Temperature Compensation Probe Connect a...

Page 22: ...able voltage power supply up until the alarm activates Adjust the Alarm Output High trimpot to set the alarm limits Use the same procedure to adjust the Alarm Output Low limits See Figure 6 Alarm Conf...

Page 23: ...arranty is not provided the authorized battery vendor s warranty shall be assigned to the batteries Note that batteries operational limits are typically more constrained than Enatel manufactured equip...

Page 24: ...claiming implied warranties or warranties of merchantability all such warranties are limited to the greatest extent permitted by law Enatel reserves the right to change the information detailed within...

Page 25: ...Enatel DC System Manual Page 25 of 26 Model RWxxx Version 3 6 This page is intentionally left blank...

Page 26: ...Enatel 66 Treffers Road Christchurch 8042 New Zealand...

Reviews: