EMTRON ELC USER MANUAL
WWW.EMTRON.WORLD
© EMTRON AUSTRALIA PTY LTD MARCH 2018
26
Fault 1/2
–
Start BIT 40
Length 8 BITS
Bit 0/1: Virtual Ground
0 = Error: Short to ground
1 = Error: IC Power Supply Low
2 = Error: Short to Vbatt
3 = Ok
Bit 2/3: Nernst Cell
0 = Error: Short to ground
1 = Error: IC Power Supply Low
2 = Error: Short to Vbatt
3 = Ok
Bit 4/5: Pump Current
0 = Error: Short to ground
1 = Error: IC Power Supply Low
2 = Error: Short to Vbatt
3 = Ok
Bit 6/7: Heater
0 = Error: Short to ground
1 = Error: IC Open Load
2 = Error: Short to Vbatt
3 = Ok
Status 1/2 - Start BIT 48
Length 8 BITS
0 = OFF
1 = Normal Operation
2 = Sensor Warming up
3 = RPM Lockout (when available)
4 = Post Start Lockout (when available)
5 = Reading Calibration Data
14 = Heater Under Temperature (cannot reach 650 DegC)
15 = Heater Over Temperature
16 = Sensor Shutdown - Thermal Shock
17 = Cannot read Chip ID
18 = Set Pump reference command Invalid
19 = Calibrate Command Invalid
20 = Standalone Command Invalid
21 = Nernst Cal Data Invalid
22 = Pump Cal Data Invalid
19 = Lambda Stability Error
20 = Error Reading Chip ID
22 = System Voltage Low
22 = Cannot enter Calibration mode
23 = Cannot enter standalone mode