3.10 INPUT/OUTPUT CONTROL CONNECTIONS 

To avoid 'interference pick up' all input and output control cables should be kept as short as 
possible and should wherever possible, be shielded. If noise free lines cannot be 
guaranteed, an interposing relay with suitable suppression must be used, this should be 
mounted as close to the 

EnviroStart

 as possible. 

 

3.11 EMISSIONS 

EnviroStart

 units produce relatively low Radio Frequency Interference (RFI) compared with 

frequency inverters and no external filters are required in normal circumstances. (See also 
Section 3.3 – Harmonics). 

 

 3.12 CABLE AND INPUT FUSE RATINGS 

Incoming fuses and power cables should generally comply with the ratings as shown in the 
table below. It is recommended that all cable be tri-rated compliant with BS 6231 and that all 
fuses be motor rated, bolt fitting, compliant with BS 88 Part 2. (It is not necessary to use 
motor rated fuses if the unit is being used in DPR Mode).  

 

MODEL 

FUSE 

RATING 

CABLE 

RATING 

 

MODEL 

FUSE 

RATING 

CABLE 

RATING 

110-SPMECG6-4A 

5A 

14A/0.75mm/20AWG 

 

220-SPMECG6-4A 

5A 

14A/0.75mm/20AWG 

110-SPMECG6-10A 

10A 

14A/1.5mm/18AWG 

 

220-SPMECG6-10A 

10A 

14A/1.5mm/18AWG 

110-SPMECG6-25A 

25A 

14A/2.5mm/14AWG 

 

220-SPMECG6-25A 

25A 

14A/2.5mm/14AWG 

110-SPMECG6-4A/60 

5A 

14A/0.75mm/20AWG 

 

220-SPMECG6-4A/60 

5A 

14A/0.75mm/20AWG 

110-SPMECG6-10A/60 

10A 

14A/1.5mm/18AWG 

 

220-SPMECG6-10A/60 

10A 

14A/1.5mm/18AWG 

110-SPMECG6-25A/60 

25A 

14A/2.5mm/14AWG 

 

220-SPMECG6-25A/60 

25A 

14A/2.5mm/14AWG 

The above detail refers to new installations, where the 

EnviroStart

 is fitted into an existing 

installation; cable should be rated according to the fuses already fitted.   

 

 

 

 

 

 

 

 

Summary of Contents for 110-SPMECG6-10A

Page 1: ...Single Phase Motor Energy Control Page 1 of 20 EnviroStart Single Phase Motor Energy Control Installation Commissioning Guide Version 2 1 January 2009 4A through 25A...

Page 2: ...t 5 When the EnviroStart is connected to the mains the output connections U V and W should be treated as being live even if the load is not being driven 6 The control I O terminals are isolated from m...

Page 3: ...8 LIGHTNING STRIKE 8 3 9 CONTROL VOLTAGE TRANSIENTS 8 3 10 INTERFACE CONNECTIONS 9 3 11 EMISSIONS 9 3 12 CABLE AND FUSE RATINGS 9 4 GENERAL INSTALLATION CONSIDERATIONS 10 4 1 GENERAL PROCEDURES 10 4 1...

Page 4: ...even and a half years In the unlikely event that you do need further support please contact your local EMS European Distributor or failing that contact us directly either by e mail or fax All details...

Page 5: ...ture relative humidity do affect sizing and failing to take proper notice of such conditions will invalidate any warranty associated with the system as supplied Where the EnviroStart is expected to op...

Page 6: ...directives plus IEC and local industrial standards Units must be installed by a suitably qualified person to comply with general good electrical engineering practices and regulations with strict refe...

Page 7: ...ING HUMIDITY Up to 95 Non Condensing Conformally Coated Systems Can Be Provided OPERATING TEMP 15o C to 40o C De rate current by 20 10o C ALTITUDE 4000m Above Sea Level De rate Current by 1 100m Above...

Page 8: ...TS Ltd of Bromsgrove Worcestershire 18th July 2003 3 4 HEAT LOSSES For heat calculation purposes it should be assumed that EnviroStart units have a power loss of 4W A at full conduction 3 5 CONTROL PA...

Page 9: ...in the table below It is recommended that all cable be tri rated compliant with BS 6231 and that all fuses be motor rated bolt fitting compliant with BS 88 Part 2 It is not necessary to use motor rat...

Page 10: ...circuit board Make sure the earth cables are connected between the box lid and circuit board terminal block and replace the lid If the EnviroStart has been pre wired then the cable supplied may be eit...

Page 11: ...tor N Base Plate Connector Motor Feed Neutral Earth Base Plate Connector Earth 4 2 SETTING UP All EnviroStart DIP Switches are polled continuously and it should be possible to make changes whilst the...

Page 12: ...ckering on and off and the motor remains stable throughout any load variations including re starts if the unit is externally controlled by say a thermostat or PLC then you may want to try Automatic Mo...

Page 13: ...following settings can be made The settings correspond to limiting how far the voltage applied to the motor will drop The lower the drop in voltage the more power savings will be achieved The reason...

Page 14: ...he voltages shown in Table 3 are not absolute but indications only Input voltage and load conditions will cause the output voltage to change from that shown based on a supply voltage of 220V 4 3 4 SOF...

Page 15: ...RS LED 1 Energy Save Enabled On to indicate that unit is running in energy save mode and is within a pre set band of energy savings around the level as is set by DIP Switches 2 3 and 4 LED 2 Power On...

Page 16: ...Single Phase Motor Energy Control Page 16 of 20...

Page 17: ...Single Phase Motor Energy Control Page 17 of 20 5 2 GENERALISED INSTALLATION DIAGRAM INSTALLATION AND COMMISSIONING GUIDE END...

Page 18: ...NDIX 1 CONNECTION AND WIRING DIAGRAM 4A AND 10A Cable Connection Main Supply with Auxiliary 240V Connection DIP Switch Setting MEC Mode and Saving Levels Indicators showing Power On Run and Fault Cond...

Page 19: ...Single Phase Motor Energy Control Page 19 of 20 CONNECTION AND WIRING DIAGRAM 25A NO PICTURE IS AVAILABLE AT THIS TIME...

Page 20: ...Single Phase Motor Energy Control Page 20 of 20 APPENDIX 2 Mechanical Drawings 25A 4A and 10A...

Reviews: