EMS 110-SPMECG6-10A Installation & Commissioning Manual Download Page 8

 
 

 

Single Phase Motor Energy Control - Page 8 of 20 

3.3 HARMONICS 

The EnviroStart

 Single Phase Motor Energy Control, like all electronic systems, does 

produce low-level harmonics during operation. The SDPMEC is however a controlled 
systems, switching taking place at or very near to the zero crossover points of the 
waveforms therefore significantly reducing radiated and communicated harmonic content.  

As the 

EnviroStart

 units produce negligible harmonic levels during normal running it is 

excluded from the constraints of such specifications by definition; however with our policy of 
ensuring maximum compliance and minimum environmental pollution our design standards 
ensure that we fall well below the limits set.

 

Typical test values* of harmonic currents on an 

EnviroStart

 controlled motor operating in Energy Save Mode yielded <14% for 5

th

 

Harmonic and <4% for 7th harmonic, significantly within the accepted and specified limits. 

Maximum limits are unlikely to be exceeded in normal operation even during ramp up and 
ramp down periods. 

*Taken from test report produced by CTS Ltd of Bromsgrove, Worcestershire 18

th

 July 2003 

 

3.4 HEAT LOSSES 

For heat calculation purposes it should be assumed that EnviroStart units have a power loss 
of 4W/A at full conduction,  

 

3.5 CONTROL PANELS/CABINETS WITH MULTIPLE UNITS  

If more than one 

EnviroStart

 is to be installed in a single enclosure the heat dissipation 

figures should be added together before selecting cooling system requirements. 

 

3.6 IMMUNITY FROM INTERFERENCE 

EnviroStart

 generally has a high level of immunity to externally generated interference and 

as a zero volt switching control is a minimal contributor.  

 

3.7 COIL SUPPRESSION 

Any coil that is connected to the 

EnviroStart

, shares a common control supply or is 

mounted in the same enclosure must be suppressed using RC circuits.  

 

3.8 LIGHTNING STRIKES/VERY HIGH VOLTAGE TRANSIENTS 

In areas subject to frequent lightning strikes or other high voltage transients, a suitably rated 
metal oxide Varistor (MOV) or transient voltage suppressor (TVS) should connect each 
input line to earth. 

 

3.9 CONTROL VOLTAGE TRANSIENTS 

Where the control supply to the 

EnviroStart

 is thought to be subject to mains-borne 

interference a suitable line filter with transient interference suppression should be fitted 
between the control supply and the 

EnviroStart

Summary of Contents for 110-SPMECG6-10A

Page 1: ...Single Phase Motor Energy Control Page 1 of 20 EnviroStart Single Phase Motor Energy Control Installation Commissioning Guide Version 2 1 January 2009 4A through 25A...

Page 2: ...t 5 When the EnviroStart is connected to the mains the output connections U V and W should be treated as being live even if the load is not being driven 6 The control I O terminals are isolated from m...

Page 3: ...8 LIGHTNING STRIKE 8 3 9 CONTROL VOLTAGE TRANSIENTS 8 3 10 INTERFACE CONNECTIONS 9 3 11 EMISSIONS 9 3 12 CABLE AND FUSE RATINGS 9 4 GENERAL INSTALLATION CONSIDERATIONS 10 4 1 GENERAL PROCEDURES 10 4 1...

Page 4: ...even and a half years In the unlikely event that you do need further support please contact your local EMS European Distributor or failing that contact us directly either by e mail or fax All details...

Page 5: ...ture relative humidity do affect sizing and failing to take proper notice of such conditions will invalidate any warranty associated with the system as supplied Where the EnviroStart is expected to op...

Page 6: ...directives plus IEC and local industrial standards Units must be installed by a suitably qualified person to comply with general good electrical engineering practices and regulations with strict refe...

Page 7: ...ING HUMIDITY Up to 95 Non Condensing Conformally Coated Systems Can Be Provided OPERATING TEMP 15o C to 40o C De rate current by 20 10o C ALTITUDE 4000m Above Sea Level De rate Current by 1 100m Above...

Page 8: ...TS Ltd of Bromsgrove Worcestershire 18th July 2003 3 4 HEAT LOSSES For heat calculation purposes it should be assumed that EnviroStart units have a power loss of 4W A at full conduction 3 5 CONTROL PA...

Page 9: ...in the table below It is recommended that all cable be tri rated compliant with BS 6231 and that all fuses be motor rated bolt fitting compliant with BS 88 Part 2 It is not necessary to use motor rat...

Page 10: ...circuit board Make sure the earth cables are connected between the box lid and circuit board terminal block and replace the lid If the EnviroStart has been pre wired then the cable supplied may be eit...

Page 11: ...tor N Base Plate Connector Motor Feed Neutral Earth Base Plate Connector Earth 4 2 SETTING UP All EnviroStart DIP Switches are polled continuously and it should be possible to make changes whilst the...

Page 12: ...ckering on and off and the motor remains stable throughout any load variations including re starts if the unit is externally controlled by say a thermostat or PLC then you may want to try Automatic Mo...

Page 13: ...following settings can be made The settings correspond to limiting how far the voltage applied to the motor will drop The lower the drop in voltage the more power savings will be achieved The reason...

Page 14: ...he voltages shown in Table 3 are not absolute but indications only Input voltage and load conditions will cause the output voltage to change from that shown based on a supply voltage of 220V 4 3 4 SOF...

Page 15: ...RS LED 1 Energy Save Enabled On to indicate that unit is running in energy save mode and is within a pre set band of energy savings around the level as is set by DIP Switches 2 3 and 4 LED 2 Power On...

Page 16: ...Single Phase Motor Energy Control Page 16 of 20...

Page 17: ...Single Phase Motor Energy Control Page 17 of 20 5 2 GENERALISED INSTALLATION DIAGRAM INSTALLATION AND COMMISSIONING GUIDE END...

Page 18: ...NDIX 1 CONNECTION AND WIRING DIAGRAM 4A AND 10A Cable Connection Main Supply with Auxiliary 240V Connection DIP Switch Setting MEC Mode and Saving Levels Indicators showing Power On Run and Fault Cond...

Page 19: ...Single Phase Motor Energy Control Page 19 of 20 CONNECTION AND WIRING DIAGRAM 25A NO PICTURE IS AVAILABLE AT THIS TIME...

Page 20: ...Single Phase Motor Energy Control Page 20 of 20 APPENDIX 2 Mechanical Drawings 25A 4A and 10A...

Reviews: