12430-3-0903

GENERAL : 

All furnaces have been fire-tested to check for

proper operation. This includes, main burner flame, pilot flame,
fan operation, fan control, limit control and automatic valve
operation. If the furnace fails to function on initial installation, it
is advisable to re-check the following:

1.

115 volts to the junction box.

2.

Inlet gas pressure.

3.

The 24 volt system.

4.

Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be
contacted to assist in servicing furnace.

Standing Pilot Model
Servicing the Pilot and Main Burners, Pilot Orifice,
Thermocouple, and Main Burner Orifices: 

Disconnect the gas

supply at the inlet to the control valve. Then remove the burner
door to gain access to the above listed components.

Spark Igniter Does Not Light Pilot: 

With air in the gas line, such

as when the furnace is first installed or was off all summer, the
pilot flame may be too lean to ignite on the first few trials. Turn
the control valve knob to pilot position and depress the red reset
button. Holding the button down continually to bleed the line;

1.

Use lighter rod to light pilot with a match.

2.

Use the piezo ignitor at 30 second intervals until it lights.

If Electrode Does Not Produce Spark:

1.

Check wire connections.

2.

Check gap for pilot burner to the electrode tip. Should be
between 1/8" (3mm) and 3/16" (4.8mm). Electrode wire
and tip must be more than 1/4" (6.3mm) away from all
other metal components.

If Pilot Does Not Light By Any Means:

1.

Check valve knob for being in the "Pilot" position.

2.

Check pilot adjustment for being full open
(counterclockwise to open).

3.

If gas is available in the supply tubing, the pilot orifice and/
or pilot burner is probably restricted by a spider web. Clean
pilot assembly and relight.

SERVICE AND MAINTENANCE SUGGESTIONS

If Pilot Does Not Remain On After Releasing Knob:

1.

Follow instructions and hold button down longer and
harder.

2.

Determine if pilot flame extends past thermocouple; if not,
adjust input or clean pilot burner.

3.

Replace thermocouple if millivolts read less than 15
millivolts.

Pilot Outage During Normal Operation:

1.

Check air inlet tube for a good tight fit at both ends (6"
diameter tube).

2.

Check burner door and pilot hole cover for tight seal.

3.

Ch\eck input by manifold pressure gauge or gas meter.

Main Gas Valve Does Not Open When Thermostat Is Turned
To On:

1.

Check for 24 volts to valve by removing one wire and
touching to the 

SAME TERMINAL 

it was on. Terminal

should have a light spark. 

DO NOT SHORT ACROSS

TERMINALS, AS IT WILL BURN OUT THE WALL
THERMOSTAT.

2.

Thermostat wires at the wall may be shorted, so check for
a faulty thermostat.

3.

To check for line voltage to furnace, remove front panel
and short across two-terminal fan control to allow fan to
operate.  (Figure 14)

Cleaning Combustion (Exchanger) Assembly

A QUALIFIED SERVICE PERSON should remove the
combustion (exchanger) assembly and flue baffles. Apply air
pressure to the inside of the combustion (exchanger) assembly
and flue baffles in order to clear all passageways.

Oiling the Motor

The fan motor should be cleaned and oiled once each heating
season. Oil holes are located on the top at each end of the motor.
Use a few drops of #10 motor oil. To clean the motor, blow air
through its ventilation openings with a vacuum cleaner or low
pressure air source.

Summary of Contents for DVC-35-1IP

Page 1: ...plier s instructions Ifyoucannotreachyourgassupplier call the fire department Installation and service must be per formed by a qualified installer service agency or the gas supplier WARNING If not ins...

Page 2: ...Standing Pilot Lighting Instructions 11 DVC 35IP Intermittent Pilot Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 14 Wiring 14 15 Service and Maintenance S...

Page 3: ...by a qualified service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imperative that control compartments burners andcirculatingairpass...

Page 4: ...service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of n...

Page 5: ...ing vehicle Qualified Installing Agency Installationandreplacementofgaspiping gasutilizationequipment or accessories and repair and servicing of equipment shall be performedonlybyaqualifiedagency Thet...

Page 6: ...orized installer for installation or relocation Compoundsusedonthreadedjointsofgaspipingshallberesistant to the action of liquefied petroleum gases The gas lines must be checked for leaks by the insta...

Page 7: ...ts in unsatisfactory performance 3 The DVC 35 can be attached to the wall or recessed into the wall up to 9 1 2 241mm in depth but the minimum 3 4 19mm vent air intake system wall depth must be main t...

Page 8: ...1 25mm provided screws 9 Installation of SOR 1 is completed Side outlet kit SOK 1 10 254mm boot assembly with regis ter for warm air discharge into an adjoining room may be installed on either side o...

Page 9: ...2mm diameter air inlet tube is placedasfaraspossibleontothecollaroftheairdropassembly Mark the 6 152mm diameter air inlet tube 1 2 13mm beyondtheoutsidewall Remove6 152mm diameterairinlet tube from co...

Page 10: ...the wind on one side of the air inlet section will result in back pressure on the flue section smothering the flame and eventual pilot outage When the vent cap is to be installed on vinyl siding or i...

Page 11: ...control knob slightly and turn clock wise to OFF Do not force 5 Replace control access panel lower front panel LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Set the thermostat to l...

Page 12: ...n to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting...

Page 13: ...tor which lights a pilot that in turn lights the main burner The gas valve used in this system is a step opening whichopensatalowerpressureforignitionandthenstepstoafull inlet pressure of 4 H2 O press...

Page 14: ...r in the absence of local codes with the National Electrical Code ANSI NFPA 70 or Canadian Electrical Code CSA C22 1 if an external electrical source is utilized This appliance is equipped with a thre...

Page 15: ...OUTLET PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCR EW GAS FLOW IG NITOR C ONTROL TO 24 V THERMOSTA T TO 24 V COMMON ON TRANSFOR MER TO 24V HOT ON TRANSFORMER WIRING I P MODEL GAS VALVE AND WIRING IGNI...

Page 16: ...Check pilot adjustment for being full open counterclockwise to open 3 Ifgasisavailableinthesupplytubing thepilotorificeand orpilotburnerisprobablyrestrictedbyaspiderweb Clean pilot assembly and religh...

Page 17: ...Second Flame Failure Recycle Delay YES YES YES NO Pilot Valve Ignition OFF Wait for Flame Signal to Disappear 1 Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame ha...

Page 18: ...and Back ON Main Burner Lights Replace SmartValve Control Check Transformer and Line Volt Supply Check that Pilot Flame Makes Good Contact with Pilot Burner Flame Rod Check for Good Electrical Connect...

Page 19: ...666 INNERFRONTASSEMBLY CANADA 21 DV 1253 INNERSHIELDCOVERPLATE 2 REQUIRED 22 DV 1252 INNERSHIELD LEFT INCLUDES NO 22 23 DV 1257 EXCHANGERASSEMBLY 24 R 3162 FILTER 25 R 3163 FILTERRETAINER 26 R 3232 PI...

Page 20: ...VIEW Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623 PH 1 800 851 3153 PH 1 618 233 7420 FAX 1 800 443 8648 FAX 1 618 233 7097 E MAIL info empirecomfort com WEB S...

Reviews: