background image

26497-1-0310

Page 29

If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the 

gas quality or pressure is low, contact your local gas supplier immediately.

1.  When ignitor button is pressed, there is no spark at ODS/

pilot. 

a.  Ignitor electrode positioned wrong - Replace pilot.

b.  Ignitor electrode is broken - Replace pilot.

c.  Ignitor electrode not connected to ignitor cable - Reconnect 

ignitor cable.

d.  Ignitor cable pinched or wet. Keep ignitor cable dry - Free 

ignitor cable if pinched by any metal or tubing. 

e.  Broken ignitor cable - Replace ignitor cable.

f.  Bad piezo ignitor - Replace piezo ignitor.

2.  Appliance produces unwanted odors.

a.  Appliance burning vapors from paint, hair spray, glues, 

etc. - Ventilate room. Stop using odor causing products 

while heater is running.

b.  Gas leak - Locate and correct all leaks.

3.  Appliance shuts off during use. (pilot and main burner are 

off.)

a.  Not enough fresh air is available for ODS/pilot to operate 

- Open window and/or door for ventilation.

b.  Low line pressure - Contact local gas company.

c.  ODS/pilot is partially clogged - Clean ODS/pilot.

d.  Defective thermocouple - Replace pilot.

4.  Appliance shuts off during use. (pilot stays on.)

a.  Low line pressure - Check line pressure to the valve.

b.  Defective  thermopile  -  Check  pilot  flame,  check  wire 

connections, output should be a minimum of 325 millivolts 

across.  TH/TP  and  TP  terminals  with  ON/OFF  switch 

off.

5.  Gas odor even when control knob is in OFF position.

a.  Gas leak - Locate and correct all leaks.

b.  Control valve defective - Replace control valve.

6.  When ignitor button is pressed, there is spark at ODS/pilot, 

but no ignition.

a.  Gas supply turned off or manual shutoff valve closed - 

Turn on gas supply or open manual shutoff valve.

b.  Control knob not in PILOT position - Turn control knob 

to PILOT position.

c.  Control knob not pressed in while in PILOT position - 

Press in control knob while in PILOT position.

d.  Air in gas lines when installed - Continue holding down 

control  knob.  Repeat  igniting  operation  until  air  is 

removed.

e.  ODS/pilot is clogged - Replace ODS/pilot assembly or 

get it serviced.

f.  Gas  regulator  setting  is  not  correct  -  Replace  gas 

regulator. 

7.  oDS/pilot lights but flame goes out when control knob is 

released.

a.  Control knob not fully pressed in - Press in control knob 

fully.

b.  Control knob not pressed in long enough - After ODS/

pilot lights, keep control knob pressed in 30 seconds.

c.  Manual Shutoff valve not fully open - Fully open manual 

shutoff valve.

d.  Thermocouple connection loose at control valve - Hand 

tighten until snug, then tighten 1/4 turn more.

e.  Pilot  flame  not  touching  thermocouple,  which  allows 

thermocouple to cool, causing pilot flame to go out. This 

problem could be caused by either low gas pressure or 

dirty or partially clogged ODS/pilot - Contact local gas 

company. 

f.  Thermocouple damaged - Replace thermocouple.

g.  Control valve damaged - Replace control valve.

8.  Burner does not light after ODS/pilot is lit.

a.  Burner orifice clogged - Clean burner or replace main 

burner orifice.

b.  Burner  orifice  diameter  is  too  small  -  Replace  burner 

orifice.

c.  Inlet gas pressure is too low - Contact qualified service 

person. 

9.  If burning at main burner orifice occurs (a loud, roaring 

blow torch noise).

a.  You must turn off burner assembly and contact a qualified 

service person.

b.  Manifold  pressure  is  too  low  -  Contact  local  gas 

company.

c.  Burner orifice clogged - Clean burner or replace burner 

orifice.

10.  Logs appear to smoke after initial operation.

a.  Vapors from paint or curing process of logs - Problem will 

stop after a few hours of operation. Run the heater with 

the damper open if you have one, or open a window for 

the first few hours. 

 

Log heater is intended to be smokeless. Turn OFF heater 

and call qualified service person.

11.  Heater produces a whistling noise when main burner is 

lit.

a.  Turning control knob to HIGH position when main burner 

is cold - Turn control knob to LOW position and let warm 

up for a minute.

b.  Air in gas line - Operate burner until air is removed from 

line. Have gas line checked by local gas company.

c.  Dirty or partially clogged burner orifice - Clean burner or 

replace burner orifice.

12.  No gas to pilot.

a.  LP-regulator  shut  down  due  to  inlet  pressure  too  high 

- Verify LP tank regulator is installed and set at 11" to  

13" w.c. Replace regulator on heater.

Turn appliance OFF and allow to cool before servicing. Only a qualified service person should service and repair the heater.

TROUBLESHOOTING

SYMPTOMS - POSSIBLE CAUSES AND CORRECTIONS

Summary of Contents for VFP20IN20

Page 1: ...aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not con...

Page 2: ...wer Accessory Information 18 VFP20IN Log Placement 19 VFP20IN Ember Placement Photos 20 VFP28IN Log Placement 21 VFP28IN Ember Placement Photos 22 Hydraulic Thermostat Lighting Instrutions 23 Millivol...

Page 3: ...ure and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room with the appliance Do not place clothing or other flammable ma...

Page 4: ...rform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls...

Page 5: ...by bending the shutter cap holding the orifice to the inlet of the venturi tube Ceiling Fans Portable Fans or Logs Installed Near Cold Air Returns Ceiling fans or oscillating floor type fans need to...

Page 6: ...affect the Btu output of the unit Contact the gas company for the heating value Contact the manufacturer or your gas company before changing spud orifice size WARNING This appliance is equipped for na...

Page 7: ...r Opening Full Open 1 8 VFP20IN2 L LP NAT Input Btu hr Maximum 20 000 20 000 Btu hr Minimum 10 000 10 000 Orifice 55 43 Air Shutter Opening Full Open 1 8 VFP20IN3 L LP NAT Input Btu hr Maximum 20 000...

Page 8: ...e The following statement is also provided on a separate label plate in the instruction packet Prior to installation of the fireplace insert the installer must mechanically secure this warning plate t...

Page 9: ...blower 120V 60Hz 1 Amp Proper opening size of fireplace required for installation of the fireplace insert A D C B Figure 2 VF FIREPLACE INSERT DIMENSIONS MODEL A B C D E F G H I J K VFP20IN 19 3 4 28...

Page 10: ...ront of the fireplace flush with a wall If installing a mantel above the fireplace you must follow the clearances shown in Figures 9 and 10 Follow the instructions below to install the fireplace in th...

Page 11: ...o areas such as joints around window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at other o...

Page 12: ...om see option 3 Figure 5 Each ventilation grill or opening shall have a minimum free area of one square inch per 1 000 BTUH of the total input rating of the gas equipment in the confined space Figure...

Page 13: ...alvemustbedisconnected fromsupplypipingsystemduringanypressuretestingofthatsystem at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the gas supply piping system by clo...

Page 14: ...the burner pressure which should be checked at the pressure test point Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Use test point A clos...

Page 15: ...the mantel of your fireplace This is a fire hazard Figure 11 No greeting cards stockings or ornamentation of any type should beplacedonorattachedtothefireplace Thisisaheatingappliance The flow of hea...

Page 16: ...surround panel assembly slightly until the bot tom return flange top panel is positioned over the top flange on the insert This secures the surround panel assembly to the insert without screws Traditi...

Page 17: ...FINISHING THE FIREPLACE INSERT NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE IN SERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OV...

Page 18: ...r to shut off automatically Note The blower shut off times will vary on blower speed and BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instruc...

Page 19: ...on burner pan 4 Compare the completed log installation with the appropriate photo from page 20 Review previous steps to make any necessary adjustments 5 Log placement is completed Attention Do not use...

Page 20: ...26497 1 0310 Page 20 Do not cover any large rear ports with loose material glowing embers VFP20IN EMBER PLACEMENT PHOTOS...

Page 21: ...log 5 Compare the completed log installation with the photo on page 22 Review previous steps to make any necessary adjustments 6 Log placement is completed 7 Attach log placement plate to cable holdin...

Page 22: ...0 Page 22 Photo 1 Photo 2 Photo 3 Photo 4 Do not cover any large rear ports with loose material glowing embers Do not cover any large front ports with loose material glowing embers VFP28IN EMBER PLACE...

Page 23: ...ion or gas flow to the appliance is shut off the pilot cannot be relighted until the safety magnet is de energized approximately 60 seconds There will be an audible click when the safety magnet in the...

Page 24: ...LOT to OFF unless knob is pushed in slightly Do not force 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety informa ti...

Page 25: ...ontrol knob slightly and turn clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If...

Page 26: ...t 2 3 hours with the burner at the highest setting Provide maximum ventilation by opening windows or doors to allow odors to dissipate Any odors remaining after this initial break in will be slight an...

Page 27: ...ll cause the thermocouple to cool When the thermocouple cools the heater will shut down MILLIVOLT PILOT Correct Pilot Flame Pattern Figure 22 Incorrect Pilot Flame Pattern Figure 23 If pilot flame pat...

Page 28: ...the remote receiver must be placed to the right of the gas valve Install remote control receiver behind bottom louver Refer to remote control installation and operating instructions for more details o...

Page 29: ...rrect Replace gas regulator 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enoug...

Page 30: ...OL VFP20IN23L 10 P265 ORIFICE 42 NAT 10 P182 ORIFICE 53 LPG 29 R5171 PILOT NAT 29 R5170 PILOT LPG 30 R2479 REGULATOR 6 0 W C NAT 30 R2480 REGULATOR 10 0 W C LPG 31 P239 NIPPLE 3 8 NPT X 1 1 2 32 26012...

Page 31: ...10 Page 31 3 9 14 4 2 3 6 1 8 10 11 12 13 15 MILLIVOLT VALVE ASSEMBLY HYDRAULIC VALVE ASSEMBLY 40 37 38 36 7 14 39 16 5 7 17 18 19 20 21 22 23 24 25 26 27 27 25 16 17 29 30 31 32 33 34 35 28 VFP20IN P...

Page 32: ...Y 23 26161 VALVE BRACKET 26 R2423 CONNECTOR MALE 39 24925 BLOWER SUB ASSEMBLY WITH MOUNTING PLATE PAD 40 18879 RHEOSTAT ASSEMBLY SPEED CONTROL 41 R7649 FAN CONTROL 42 R2204 CORD SET 43 R7912 WIRE HARN...

Page 33: ...0 Page 33 VFP28IN PARTS VIEW 5 3 4 6 3 1 2 7 8 9 10 11 12 13 14 15 16 17 18 22 24 23 25 26 27 28 29 19 20 31 32 33 34 35 36 30 37 MILLIVOLT VALVE ASSEMBLY HYDRAULIC VALVE ASSEMBLY 38 43 40 41 39 7 21...

Page 34: ...cription VFP28IN LOG SET 1 R8301 REAR LOG 2 R8299 LEFT FRONT LOG 3 R8300 RIGHT FRONT LOG 4 R8302 Y BRANCH LOGS PARTS LISTS PARTS VIEWS Use Only Manufacturer s Replacement Parts Use of Any Other Parts...

Page 35: ...rmation beyond what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finis...

Page 36: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Page 37: ...26497 1 0310 Page 37 SERVICE NOTES...

Page 38: ...26497 1 0310 Page 38 SERVICE NOTES...

Page 39: ...26497 1 0310 Page 39 SERVICE NOTES...

Page 40: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: