background image

26497-1-0310

Page 11

Water vapor is a by-product of gas combustion.  An unvented room 

heater produces approximately one (1) ounce (30ml) of water for 

every 1,000 BTU's (.3KW's) of gas input per hour. 
Unvented room heaters are recommended as supplemental heat (a 

room) rather than a primary heat source (an entire house). In most 

supplemental heat applications, the water vapor does not create a 

problem. In most applications, the water vapor enhances the low 

humidity atmosphere experienced during cold weather. 

The  following  steps  will  help  insure  that  water  vapor  does  not 

become a problem.  

1.  Be sure the heater is sized properly for the application, including 

ample combustion air and circulation air.

2.  If high humidity is experienced, a dehumidifier may be used to 

help lower the water vapor content of the air.

3.  Do  not  use  an  unvented  room  heater  as  the  primary  heat 

source.

This heater shall not be installed in a confined space or unusually 

tight  construction  unless  provisions  are  provided  for  adequate 

combustion and ventilation air.

The National Fuel Gas Code, ANSI Z223.1 defines a confined space 

as a space whose volume is less than 50 cubic feet per 1,000 Btu per 

hour (4.8m

3

 per kw) of the aggregate input rating of all appliances 

installed in that space and an unconfined space as a space whose 

volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8m

3

 

per kw) of the aggregate input rating of all appliances installed in 

that space. Rooms communicating directly with the space in which 

the appliances are installed, through openings not furnished with 

doors, are considered a part of the unconfined space.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually  tight  construction,  you  must  provide  additional  fresh 

air.

 

Unusually  tight  construction  is  defined  as  construction 

where:

a.  Walls and ceilings exposed to the outside atmosphere have 

a continuous water vapor retarder with a rating of one perm 

or less with openings gasketed or sealed, and

b.  Weather-stripping has been added on openable windows and 

doors, and

c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 

around window and door frames, between sole plates and 

floors, between wall-ceiling joints, between wall panels, at 

penetrations for plumbing, electrical, and gas lines, and at 

other openings.

  If your home meets all of the three criteria above, you must provide 

additional fresh air. See 

“Ventilation Air From Outdoors,”

 

page 12. 

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined 

space.

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.

1.  Determine the volume of the space (length x width x height).

  Length x Width x Height = 

 cu. ft. (volume of 

space)

Example:

 Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling 

height) = 1,280 cu. ft. (volume of space)

 

If additional ventilation to adjoining room is supplied with 

grills or openings, add the volume of these rooms to the total 

volume of the space.

2.  Divide the space volume by 50 cubic feet to determine the 

maximum BTU/Hr the space can support.

 

 (volume of space) ÷ 50 cu. ft. = (maximum 

BTU/Hr the space can support)

Example:

 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 

25,600 (maximum BTU/Hr the space can support)

3.  Add the BTU/Hr of all fuel burning appliances in the space.

 Vent-free heater    

 BTU/Hr

 Gas water heater   

 BTU/Hr

 Gas furnace 

 

 BTU/Hr

 Vented gas heater  

 BTU/Hr

 Gas fireplace logs  

 BTU/Hr

 Other gas appliances*  +   

 BTU/Hr

 Total 

 

 BTU/Hr

Example:

  Vented gas heater   

20,000 

BTU/Hr

  

    Vent-free heater           +  18,000 

BTU/Hr

  

    Total 

 

38,000 

BTU/Hr

*Do not include direct-vent gas appliances. Direct vent draws 

combustion air from the outdoors and vents to the outdoors.

4. Compare the maximum BTU/Hr the space can support with the 

actual amount of BTU/Hr used.

 

 BTU/Hr (maximum the space can support)

 

 BTU/Hr (actual amount of BTU/Hr used)

 

Example: 

    25,600 

BTU/Hr (maximum the space can support)

    38,000 

BTU/Hr (actual amount of BTU/Hr used)

Warning:

 If the area in which the heater may be operated is smaller 

than that defined as an unconfined space or if the building is of 

unusually  tight  construction,  provide  adequate  combustion  and 

ventilation air by one of the methods described in the 

National 

Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and 

Ventilation,

 or applicable local codes.

WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS

PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR

Summary of Contents for VFP20IN20

Page 1: ...aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not con...

Page 2: ...wer Accessory Information 18 VFP20IN Log Placement 19 VFP20IN Ember Placement Photos 20 VFP28IN Log Placement 21 VFP28IN Ember Placement Photos 22 Hydraulic Thermostat Lighting Instrutions 23 Millivol...

Page 3: ...ure and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room with the appliance Do not place clothing or other flammable ma...

Page 4: ...rform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls...

Page 5: ...by bending the shutter cap holding the orifice to the inlet of the venturi tube Ceiling Fans Portable Fans or Logs Installed Near Cold Air Returns Ceiling fans or oscillating floor type fans need to...

Page 6: ...affect the Btu output of the unit Contact the gas company for the heating value Contact the manufacturer or your gas company before changing spud orifice size WARNING This appliance is equipped for na...

Page 7: ...r Opening Full Open 1 8 VFP20IN2 L LP NAT Input Btu hr Maximum 20 000 20 000 Btu hr Minimum 10 000 10 000 Orifice 55 43 Air Shutter Opening Full Open 1 8 VFP20IN3 L LP NAT Input Btu hr Maximum 20 000...

Page 8: ...e The following statement is also provided on a separate label plate in the instruction packet Prior to installation of the fireplace insert the installer must mechanically secure this warning plate t...

Page 9: ...blower 120V 60Hz 1 Amp Proper opening size of fireplace required for installation of the fireplace insert A D C B Figure 2 VF FIREPLACE INSERT DIMENSIONS MODEL A B C D E F G H I J K VFP20IN 19 3 4 28...

Page 10: ...ront of the fireplace flush with a wall If installing a mantel above the fireplace you must follow the clearances shown in Figures 9 and 10 Follow the instructions below to install the fireplace in th...

Page 11: ...o areas such as joints around window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at other o...

Page 12: ...om see option 3 Figure 5 Each ventilation grill or opening shall have a minimum free area of one square inch per 1 000 BTUH of the total input rating of the gas equipment in the confined space Figure...

Page 13: ...alvemustbedisconnected fromsupplypipingsystemduringanypressuretestingofthatsystem at test pressures in excess of 1 2 psig 3 5kPa The appliance must be isolated from the gas supply piping system by clo...

Page 14: ...the burner pressure which should be checked at the pressure test point Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point Use test point A clos...

Page 15: ...the mantel of your fireplace This is a fire hazard Figure 11 No greeting cards stockings or ornamentation of any type should beplacedonorattachedtothefireplace Thisisaheatingappliance The flow of hea...

Page 16: ...surround panel assembly slightly until the bot tom return flange top panel is positioned over the top flange on the insert This secures the surround panel assembly to the insert without screws Traditi...

Page 17: ...FINISHING THE FIREPLACE INSERT NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE IN SERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OV...

Page 18: ...r to shut off automatically Note The blower shut off times will vary on blower speed and BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instruc...

Page 19: ...on burner pan 4 Compare the completed log installation with the appropriate photo from page 20 Review previous steps to make any necessary adjustments 5 Log placement is completed Attention Do not use...

Page 20: ...26497 1 0310 Page 20 Do not cover any large rear ports with loose material glowing embers VFP20IN EMBER PLACEMENT PHOTOS...

Page 21: ...log 5 Compare the completed log installation with the photo on page 22 Review previous steps to make any necessary adjustments 6 Log placement is completed 7 Attach log placement plate to cable holdin...

Page 22: ...0 Page 22 Photo 1 Photo 2 Photo 3 Photo 4 Do not cover any large rear ports with loose material glowing embers Do not cover any large front ports with loose material glowing embers VFP28IN EMBER PLACE...

Page 23: ...ion or gas flow to the appliance is shut off the pilot cannot be relighted until the safety magnet is de energized approximately 60 seconds There will be an audible click when the safety magnet in the...

Page 24: ...LOT to OFF unless knob is pushed in slightly Do not force 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety informa ti...

Page 25: ...ontrol knob slightly and turn clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If...

Page 26: ...t 2 3 hours with the burner at the highest setting Provide maximum ventilation by opening windows or doors to allow odors to dissipate Any odors remaining after this initial break in will be slight an...

Page 27: ...ll cause the thermocouple to cool When the thermocouple cools the heater will shut down MILLIVOLT PILOT Correct Pilot Flame Pattern Figure 22 Incorrect Pilot Flame Pattern Figure 23 If pilot flame pat...

Page 28: ...the remote receiver must be placed to the right of the gas valve Install remote control receiver behind bottom louver Refer to remote control installation and operating instructions for more details o...

Page 29: ...rrect Replace gas regulator 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enoug...

Page 30: ...OL VFP20IN23L 10 P265 ORIFICE 42 NAT 10 P182 ORIFICE 53 LPG 29 R5171 PILOT NAT 29 R5170 PILOT LPG 30 R2479 REGULATOR 6 0 W C NAT 30 R2480 REGULATOR 10 0 W C LPG 31 P239 NIPPLE 3 8 NPT X 1 1 2 32 26012...

Page 31: ...10 Page 31 3 9 14 4 2 3 6 1 8 10 11 12 13 15 MILLIVOLT VALVE ASSEMBLY HYDRAULIC VALVE ASSEMBLY 40 37 38 36 7 14 39 16 5 7 17 18 19 20 21 22 23 24 25 26 27 27 25 16 17 29 30 31 32 33 34 35 28 VFP20IN P...

Page 32: ...Y 23 26161 VALVE BRACKET 26 R2423 CONNECTOR MALE 39 24925 BLOWER SUB ASSEMBLY WITH MOUNTING PLATE PAD 40 18879 RHEOSTAT ASSEMBLY SPEED CONTROL 41 R7649 FAN CONTROL 42 R2204 CORD SET 43 R7912 WIRE HARN...

Page 33: ...0 Page 33 VFP28IN PARTS VIEW 5 3 4 6 3 1 2 7 8 9 10 11 12 13 14 15 16 17 18 22 24 23 25 26 27 28 29 19 20 31 32 33 34 35 36 30 37 MILLIVOLT VALVE ASSEMBLY HYDRAULIC VALVE ASSEMBLY 38 43 40 41 39 7 21...

Page 34: ...cription VFP28IN LOG SET 1 R8301 REAR LOG 2 R8299 LEFT FRONT LOG 3 R8300 RIGHT FRONT LOG 4 R8302 Y BRANCH LOGS PARTS LISTS PARTS VIEWS Use Only Manufacturer s Replacement Parts Use of Any Other Parts...

Page 35: ...rmation beyond what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finis...

Page 36: ...m Parts Heater Hearth and Grills Victor Division of F W Webb Company 200 Locust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites...

Page 37: ...26497 1 0310 Page 37 SERVICE NOTES...

Page 38: ...26497 1 0310 Page 38 SERVICE NOTES...

Page 39: ...26497 1 0310 Page 39 SERVICE NOTES...

Page 40: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: