INTRODUCTION

• 

When the appliance is connected to a fixed piping system, 

the installation must conform with local codes, or in the ab-

sence of local codes with the 

National Fuel Gas Code, ANSI 

Z223.1/NFPA 54

, or 

International Fuel Gas Code

.

• 

When installed, the appliance must be electrically grounded 

in accordance with local codes, or in the absence of local 

codes with the 

National Electrical Code, ANSI/NFPA 70

, if 

applicable.

• 

Solid fuels shall not be burned in this appliance.

• 

The maximum gas inlet supply pressure is 13" for LP and 

10.5" for NAT.

• 

For appliances for fixed fuel piping system and equipped 

with an appliance gas pressure regulator, the required mani

-

fold pressure in inches water column: 10" for LP and 3.5" 

NAT.

• 

For appliances for fixed fuel piping system and equipped 

with an appliance gas pressure regulator, the appliance and 

its individual shutoff valve must be disconnected from the 

gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 psi (3.5 kPa). 

The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psi (3.5 kPa).

For an appliance designed for use with a non-disposable self-

contained LP-gas supply system:

• 

Propane cylinders may be acceptable for use with the ap-

pliance provided they are are compatible with the appliance 

retention means. 

• 

LP-gas supply cylinder must be constructed and marked 

in accordance with the 

U.S. Department of Transportation 

(D.O.T.) Specifications for LP-Gas Cylinders

, or the 

Stan

-

dard for Cylinders, Spheres and Tubes for Transportation 

of Dangerous Goods and Commission, CAN/CSA-B339

 as 

applicable. 

• 

LP-gas supply cylinders betweent 4 and 40 pounds must 

have an overfill prevention device.

• 

LP-gas supply cylinder must have a connection device com-

patible with the connection of the appliance.

• 

If the appliance is equipped with a CGA No. 600 Cylinder 

Connection Device, the cylinder must be disconnected when 

the appliance is not in use.

• 

If appliance is to be permanently connected to a gas piping 

system from a remote supply tank, installation must be in ac-

cordance with local codes or, in the absence of local codes, 

with the 

National Fuel Gas Codes ANSI Z223.1/NFPA 54.

Enclosures for LP-gas supply cylinders shall be ventilated by 

openings at the level of the cylinder valve and at floor level. The 

effectiveness of the opening(s) for purposes of ventilation shall 

be determined with the LP-gas supply cylinder(s) in place. This 

shall be accomplished by one of the following.

a.  One side of the enclosure shall be completely open; or

b.  For an enclosure having four sides, a top and a bottom:

1.  At least two ventilation openings at cylinder valve 

level shall be provided in the side wall, equally 

sized, spaced at 180 degrees (3.14rad), and unob-

structed. Each opening shall have a total free area 

of not less than 1/2 square inch per pound (2.3 sq. 

cm/kg) of stored fuel capacity and not less than a 

total free area of 10 square inches (64.5 sq. cm).

2.  Ventilation opening(s) shall be provided at floor 

level and shall have a total free area of not less 

than 1/2 square inch per pound (3.2 sq. cm/kg) of 

stored fuel capacity and not less than a total free 

area of 10 square inches (64.5 sq. cm). If ventila

-

tion openings at floor level are in a side alll, there 

shall be at least two openings. The bottom of the 

openings shall be at floor level and the upper edge 

no more than 5 inches (127 mm) above the floor. 

The openings shall be equally sized, spaced at 180 

degrees (3.14 rad) and unobstructed.

3.  Every opening shall have minimum dimensions so 

as to permit the entrance of a 1/8 inch (3.2 mm) 

diameter rod.

• 

Cylinder valves shall be readily accessible for hand opera-

tion. A door on the enclosure to gain access to the cylinder 

valves is acceptable, provided it is non-locking and can be 

opened without the use of tools.

• 

There shall be a minimum clearance of 2 inches (51 mm) 

between the lower surface of the floor of the LP-gas supply 

cylinder enclosure and the ground.

• 

The design of the appliance shall be such that (1) the LP-gas 

supply cylinder(s) can be connected, disconnected and the 

connections inspected and tested outside the cylinder en-

closure; and (2) those connections which could be disturbed 

when installing the cylinder(s) in the enclosure can be leak 

tested inside the enclosure;

Cleaning Instructions

This appliance is built using mostly high-grade stainless steel to 

resist rust-through. In outdoor applications, all stainless steel will 

develop a dull patina and, depending on the local environment 

and on the materials used in the installation, may develop some 

surface oxidation (rust). This does not affect the performance of 

the fireplace, and does not require any action to correct. If you 

prefer keeping your fireplace front looking factory-fresh, clean it 

as required with stainless steel cleaner.

When installation application includes highly acidic applications 

such as mortar or stone etching, do not remove the protective 

PVC film from the stainless steel until after this application is 

complete. Once the film has been removed we recommend that 

the appliance be cleaned with a stainless steel cleaner immedi-

ately.

Please note that areas where the film has been formed (corners, 

hems, etc.) may require extra cleaning due to the properties of 

the film. Ensure that all protective film has been removed from 

the fireplace prior to burning the appliance.  

Summary of Contents for OP36FP32M(N,P)-1

Page 1: ...RNING If the information in these instructions are not fol lowed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Improper installation adjustment...

Page 2: ...ation 11 Fireplace Framing and Installation 12 Operation Instrucitons Flame Appearance 13 OP 36 42 FP72 Lighting Instructions 14 OP 36 42 FP32 Lighting Instructions 15 Pilot and Main Burner Flame Char...

Page 3: ...to the ap pliance being into operation if there is evidence of ex cessive abrasion or wear or if the hose is damaged Inspect the burner at least once a year IMPORTANT SAFETY INFORMATION DO NOT OPERATE...

Page 4: ...erform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wall...

Page 5: ...staller 1 Installer must leave instruction manual with owner after installation 2 Installer must have owner fill out and mail warranty card supplied with this fireplace 3 Installer should show owner h...

Page 6: ...of the enclosure shall be completely open or b For an enclosure having four sides a top and a bottom 1 At least two ventilation openings at cylinder valve level shall be provided in the side wall equa...

Page 7: ...al main gas cock should be located in the vicinity of the unit Where none exists or where its size or location is not adequate contact your local authorized installer for installation or relocation Co...

Page 8: ...Ceiling Clearances The ceiling height should not be less than 36 from the top of the hood Mantel Clearances Ventless fireplace models must use the hood supplied with the fireplace If a combustible man...

Page 9: ...mantel of your fireplace This is a fire hazard Figure 3 No greeting cards stockings or ornamentation of any type should be placed on or attached to the fireplace This is a heating appliance The flow o...

Page 10: ...42FP A 37 5 8 37 5 8 B 39 1 2 43 1 2 C 19 13 16 19 13 16 D 33 37 E 35 35 F 36 40 G 24 3 8 24 3 8 H 6 1 8 6 1 8 I 30 9 16 30 9 16 J 8 3 8 8 3 8 K 5 3 4 5 3 4 L 36 3 16 38 3 16 M 72 3 8 76 3 8 N 2 11 16...

Page 11: ...ude covered patio screened porch gazebo or an outside wall of a house Minimum porch area 96 square feet Minimum ceiling height 82 inches Minimum of two walls to be open or screened to the following gu...

Page 12: ...AMING REQUIRED COMBUSTIBLE MATERIAL NOT ALLOWED ADJACENT TO FIREPLACE NOTE FINISH MUST BE CONCRETE BOARD OR NON COMBUSTIBLE MATERIAL OP36FP OP42FP A 38 1 2 38 1 2 B 40 44 C 19 3 8 19 3 8 Attention Add...

Page 13: ...nd will disappear with continued use PERIODIC CLEANING Refer to parts diagram for location of items discussed below Do not use cleaning fluid to clean logs or any part of heater Logs brush with soft b...

Page 14: ...he appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE 1 Locate On Off gas cock and turn clockwise...

Page 15: ...his appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to...

Page 16: ...after the pilot orifice has been removed To Remove Pilot Orifice 1 Disconnect the pilot supply line at the pilot burner 2 Remove pilot orifice from pilot burner It may be necessary to tap on pilot bu...

Page 17: ...omponents Check 750 Millivolt System Operation Millivolt system and all individual components may be checked with a millivolt meter 0 1000 MV range Remote Receiver Use the following steps to place the...

Page 18: ...T Learn MOTOR COMM POWER IPI Continuous Pilot Off On Remote Off S I ADJ GND HI LO Solenoid ORANGE BLACK BLACK ORANGE GREEN WHITE BROWN PILOT GAS CONTROL VALVE ELECTRONIC CONTROL MODULE N A AF 4000 B P...

Page 19: ...l use if batteries are replaced or if a replacement transmitter is purchased from your dealer or the factory In order for the module to accept the transmitter security code be sure the slide button on...

Page 20: ...n control knob to PILOT position c Control knob not pressed in while in PILOT position Press in control knob while in PILOT position d Airingaslineswheninstalled Continueholdingdowncontrol knob Repeat...

Page 21: ...st Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS...

Page 22: ...27932 27932 27932 27932 Burner Support Right 18 27799 27799 27801 27801 Grate Tang Assembly 19 P253 P253 P253 P253 Orifice Fitting 20 P209 P209 P209 P209 Orifice Nat 20 P245 P245 P300 P300 Orifice LP...

Page 23: ...27777 2 0212 Page 23 PARTS VIEW 29 31 30 10 8 6 5 1 12 2 13 13 14 3 3 8 9 11 7 4 33 24 35 18 21 20 19 16 22 28 15 17 25 34 15 16 23 17 26 27 22 28 34 21 20 19 25 18 24 32...

Page 24: ...must be installed by a qualified installer and operated in accordance with the written instructions furnished with the appliance Ready access to the appliance for service is the responsibility of the...

Reviews: