10.  With  the  flex  vent  assembly  and  the  48”  long  hard  pipe 

components laid out on the floor, begin securing these parts 

together. First, apply a generous bead of silicone sealant to 

the inside of the 4” diameter flex flue (not the end with the 

pre-installaed connector), then slide the flex flue over the 4” 

diameter hard pipe flue. Be sure to overlap at least 1-1/4”. Se-

cure this connection with a 4” diameter band clamp provided. 

Be careful not to damage or tear the flex flue when tightening 

clamp.

11.  Repeat the connection process for the outer 7” diameter flex 

vent to hard pipe connection. Use silicone sealant at this joint 

also, overlap at least 1-1/4”, then secure the joint with the 7” 

diameter band clamp provided. Be careful not to damage or 

tear the flex vent pipe when tightening the clamp.

12.  While the venting is still on the floor, assemble the roof jack 

components as shown in Figure 3 and pre-install the roof jack 

assembly to the hard pipe approximately 18” from the top 

end of the hard pipe.

13.  Now the pre-assembled vent system may be carried to the 

roof, then lowered through the roof cutout opening (see step 

5). Feed the flex vent end down through the roof opening and 

firestop thimble assembly installed in step 4.

14.  Secure the roof support assembly to the roof sheathing with 

at least (4) nails/screws through each support bracket. Check 

that the combustible clearances through the roof framing will 

maintain at least a 1” clearance from the vent pipe.

15.  Determine  how  high  the  vent  terminal  should  be  located 

above the roof line based on the roof pitch information shown 

in Figure 4. Adjust the vent system height by loosening the 

pre-installed  roof  support  pipe  clamp  and  sliding  the  vent 

pipe up or down as pre-determined, then re-tighten the pipe 

clamp. Install a couple of sheet metal screws through the pipe 

clamp into the outer hard vent pipe to lock in place.

16.  Check to make sure that the bottom end of the flex vent is 

long enough to reach the fireplace adapter collars. If too long, 

trim off the extra flex vent not needed.

WING NUT (2)

PIPE CLAMP

ROOF BRACKET (2)

NUT (2)

SCREW (2)

H

X

12

ROOF PITCH IS X/12

H (Min.) - Minimum height from

roof to lowest discharge opening

DISCHARGE

LOWEST

OPENING

VENT CAP

GAS VENT

Figure 3

Figure 4

ROOF PITCH

H (Min.)

Flat to 6/12

12” (305mm)

6/12 to 7/12

15” (381mm)

Over 7/12 to 8/12

18” (457mm)

Over 8/12 to 16/12

24” (610mm)

Over 16/12 to 21/12

36” (914mm)

Summary of Contents for DVVK-4FV

Page 1: ...ted before initial use and at least annually by a quali ed eld service person Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air ow In spect entir...

Page 2: ...e Vertical Flex Termination Kit WARNING Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches 305mm above the roof WARNING Refer to your replac...

Page 3: ...his opening must be large enough to provide a mini mum 1 air space clearance from the vertical vent pipe to any combustible framing 6 Install the Firestop Thimble assembly to the framed opening in the...

Page 4: ...f cutout opening see step 5 Feed the ex vent end down through the roof opening and restop thimble assembly installed in step 4 14 Secure the roof support assembly to the roof sheathing with at least 4...

Page 5: ...that may be used as an attic insulation shield The collar can be installed around the ex pipe or hard pipe just above the restop thimble This collar will act as a shield to prevent blown in sulation...

Page 6: ...imble Ceiling Straps As Req d Venting Support With Gasket Clamps 7 Dia Adapter Collar 4 Dia Flue Connector Assembly Firestop Thimble Adjustable Storm Collar Use To Keep Keep Insulation Out Of Inlet Ve...

Page 7: ...Ply Alum Flex 7 Diameter by 6 ft MF07ALA2F006 1 5 4 7 x 48 Rigid Pipe Assembly MF100554 1 6 Firestop Thimble Assembly MF100124 1 7 Roof Flashing 0 12 to 6 12 MF100091 1 8 7 Flex Adapter Collar with G...

Page 8: ...21552 0 0506 Page 8 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: