CG Drives & Automation 01-6142-01r2
Technical Data
63
8.3
Operation at higher
temperatures
Most Emotron AC drives are made for operation at
maximum of 40°C (104 °F) ambient temperature. However,
it is possible to use the AC drive at higher temperatures with
reduced output rating.
Possible derating
Derating of output current is possible with
-1% / degree Celsius to max +15 °C (= max temp 55 °C) or
-0.55%/ degree Fahrenheit to max +27 °F
(= max temp. 131 °F).
Example
In this example we have a motor with the following data that
we want to run at the ambient temperature of
45 °C (113 °F):
Voltage
400 V
Current
72 A
Power
37 kW (50 hp)
Select AC drive
The ambient temperature is 5 °C (9 °F) higher than the
maximum ambient temperature. The following calculation
is made to select the correct AC drive model.
Derating is possible with loss in performance of
1%/°C (0.55%/ degree F).
Derating will be: 5 x 1% = 5%
Calculation for model 48-074
74 A - (5% x 74) = 70.3 A; this is not enough.
Calculation for model 48-090
90 A - (5% x 90) = 85.5 A
In this example we select the 48-090.
8.4
Operation at higher
switching frequency
Table 29 shows the switching frequency for the different AC
drive models. With the possibility of running at higher
switching frequency you can reduce the noise level from the
motor. The switching frequency is set in menu [22A],
Motor sound, see software instruction. At switching
frequencies >3 kHz derating might be needed.
Table 29
Switching frequency
Models
Standard
Switching
frequency
Range
FLD##-003 to FLD##-295
3 kHz
1.5–6 kHz
FLD##-293, -295 and -365
2 kHz
Summary of Contents for FLD48-003-54
Page 2: ......
Page 4: ......
Page 8: ...4 CG Drives Automation 01 6142 01r2...
Page 30: ...26 Installation CG Drives Automation 01 6142 01r2...
Page 56: ...52 EMC and standards CG Drives Automation 01 6142 01r2...
Page 74: ...70 Technical Data CG Drives Automation 01 6142 01r2...
Page 82: ...78 Menu List CG Drives Automation 01 6142 01r2...
Page 83: ......