22
Installation
CG Drives & Automation, 01-6142-01r2
3.4.2 Fuse data
Please refer to the chapter Technical data, section 8.7, page
66.
3.4.3 Cable connection data for mains, motor and PE cables according to
IEC ratings
NOTE: The dimensions of the power terminals used in
the cabinet drive models 300 to 3K0 can differ
depending on customer specification.
Table 13
Cable connector range and tightening torque for Emotron FLD48 and FLD52, according to IEC ratings.
Model
Frame
size
Cable cross section connector range
Cable type
Mains and motor
Brake
PE
Cable area
mm
2
Tightening
torque
Nm
Cable area
mm
2
Tightening
torque
Nm
Cable area
mm
2
Tightening
torque
Nm
FLD##-003-54
B
0.5 - 10
1.2-1.4
0.5 - 10
1.2-1.4
1.5 - 16
2.6
Copper (Cu)
75°C
FLD##-004-54
FLD##-006-54
FLD##-008-54
FLD##-010-54
FLD##-013-54
FLD##-018-54
FLD48-025-20
C2
4 - 25
2
4 - 25
2
4 - 25 *
4.3
FLD48-030-20
FLD48-036-20
FLD48-045-20
FLD48-058-20
FLD##-026-54
C
2.5-16
stranded
2.5-25 solid
1.2-1.4
2.5-16
stranded
2.5-25 solid
1.2-1.4
6-16
stranded
6-25 solid
1.2-1.4
FLD##-031-54
FLD##-037-54
FLD##-046-54
FLD48-072-20
D2
0.75 - 50
3.3
0.75 - 50
3.3
10 - 70*
4.3
FLD48-088-20
D2
16 - 50
7.9
16 - 50
7.9
FLD48-105-20
FLD##-061-54
D
10-35
stranded
10-50 solid
2.8-3
10-35
stranded
10-50 solid
2.8-3
16-35
stranded
16-50 solid
2.8-3
FLD##-074-54
FLD48-142-20
E2
16- 150
31 (for
16-34 mm
2
)
42 (for
35-150 mm
2
)
16 - 120
31 (for
16-34 mm
2
)
42 (for
35-120
mm
2
)
16- 150
16 - 185 **
31 (for
16-34 mm
2
)
42 (for
35-150 mm
2
)
10 **
FLD48-171-20
FLD48-090-54
E
FLD48-109-54
FLD48-146-54
FLD48-175-54
Summary of Contents for FLD48-003-54
Page 2: ......
Page 4: ......
Page 8: ...4 CG Drives Automation 01 6142 01r2...
Page 30: ...26 Installation CG Drives Automation 01 6142 01r2...
Page 56: ...52 EMC and standards CG Drives Automation 01 6142 01r2...
Page 74: ...70 Technical Data CG Drives Automation 01 6142 01r2...
Page 82: ...78 Menu List CG Drives Automation 01 6142 01r2...
Page 83: ......