6. INSTALLATION OF THE INDOOR UNIT
6.5.3 Power supplies cables and connecting
- All the feed and connection cables must be approved in conformance
with IEC standards, and for lengths up to 15m., must have a section
not less than:
Model
Cable
of alimentation
Cable
connection
Single Wall
3x2.5 mm
2
5x1,5 mm
2
Dual, Trial e Quadrial
3x2.5 mm
2
4x1,5 mm
2
- Use a multi-pole cable of type H07RN-F
- For lengths over 15m, use the next higher standard section, always
checking that in every case the voltage drop during operation is lower
than 3% of the supply voltage.
- If a cable is damaged it must be replaced by service personnel or by
qualified personnel.
- All cables must have the certificate of conformity.
6.6 Connection of the indoor unit to the
power supply terminal block
- Lift the frontal louver, remove the terminal strip cover by acting on the
screw,
- Insert the cable from the back side of the unit and then take it off on
the frontal side
- Loosen the screws and insert the cable ends completely in the terminal
block, after this tighten the screws.
All'unità esterna
Unità interna
70 mm
10 mm
10 mm
50 mm
- Pull lightly on the cable to make sure that the cables have been inserted
and secured properly.
- After connecting the cables, never forget to tighten them to the cable
gland.
Summary of Contents for X-REV0-1219W
Page 16: ...16 IT IT 5 POSIZIONAMENTO DELLE UNITÀ Destro Sinistro modello 18 kBtu ...
Page 17: ...17 IT IT 5 POSIZIONAMENTO DELLE UNITÀ modello 18 kBtu ...
Page 18: ...18 IT IT 5 POSIZIONAMENTO DELLE UNITÀ Destro Sinistro modello 24 kBtu ...
Page 19: ...19 IT IT 5 POSIZIONAMENTO DELLE UNITÀ modello 24 kBtu ...
Page 50: ......
Page 64: ...64 GB GB 5 UNIT POSITIONING Destro Sinistro Model 18 kBtu Left Right ...
Page 65: ...65 GB GB 5 UNIT POSITIONING Model 18 kBtu ...
Page 66: ...66 GB GB 5 UNIT POSITIONING Destro Sinistro Model 24 kBtu Left Right ...
Page 67: ...67 GB GB 5 UNIT POSITIONING Model 24 kBtu ...
Page 96: ...96 ...
Page 99: ......