6.6. Operator Pages Parameters Definetions
PROCESS SET
PID set value for selected channel is can be adjusted according to this parameter.
ALARM SET
Alarm set value for selected channel is can be adjusted according to this parameter.
LCD BACKLIGHT
Display backlight is can be controlled by this parameter value. If parameter value;
0 = LCD backlight is continuously OFF
1 = LCD backlight is continuously ON
2 = “power safe mode” If any button is not pressed during 30 secs. LCD backlight is automatically
changed OFF mode, when any button is pressed LCD backlight is changed ON mode again.
LCD CONTRAST
Display contrast value is can be controlled by this parameter value.
Channel Number
Channel
Selection Buttons
REVISION NUMBER “Software Revision Number”
Device software revision number is can be seen by this parameter.
This parameter is can not be changed, it’s only observed.
Parameter
CHANNEL-1 PROCESS SET
Address
42030
CHANNEL-2 PROCESS SET
42042
CHANNEL-3 PROCESS SET
42054
CHANNEL-4 PROCESS SET
42066
Parameter
Address
CHANNEL-1 ALARM SET
42078
CHANNEL-2 ALARM SET
42082
CHANNEL-3 ALARM SET
42086
CHANNEL-4 ALARM SET
42090
Alarm Set Parameters Modbus Addresseses
Process Set Parameters Modbus Addresses
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
*
( )
{
-
SET MAX
SET MIN
100.0
-
1700.0
-100.0
90.0
42182
2
0
1
42183
60
30
45
Parameter
Explanation
Default Address
Min.
Max.
Unit
PROCESS SET
PID Set Value For Channel-X
ALARM SET
Alarm Set Value For Channel-X
LCD BACKLIGHT
LCD Display Backlight Mode
LCD CONTRAST
LCD Display Contrast Value
O
C
O
C
-
-
Channel number is can be seen upper left side of the display and can be selected by pressing
the channel selection buttons (1, 2, 3 or 4).
ii
These parameters are displayed on LCD screen with point, so that the parameters values
are 10 times than the real values for modbus function.
ii
If no operation is performed for 20 seconds in operator parameters section, device turns to
main operation screen automatically.