SENSOR BREAK OUTPUT VALUE
(FOR HEATING PID 0.0%, 100.0%)
(FOR COOLING PID -100.0%, 0.0%)
When sensor breaks, controlling of the process can continue by entering %output
value to parameter.
If this parameter 0.0, process control output does not perform an output when sensor
breaks.
If > 0 (Dead Band)
56
If < 0 (Overlap Band)
Process
Output
100%
50%
0%
Process
Value
Heating Set
Value
( )
Cooling Set
Value
( + )
Process
Output
100%
50%
0%
Process
Value
Cooling Set
Value
( + )
Heating Set
Value
( )
Soft Start Set value
It can be adjusted from 0 to 9999 with increment and decrement buttons. When the
device power on, if the Soft start set value different from “0”, and temperature value is
lower than soft start value on heating processes, device starts soft start operation,
until temperature reaches soft start set value. On soft start device output period is
SSCt parameter value and device control output is SSCo parameter value.
Soft Start Control Output
It can be adjusted from 10% to 90% with increment and decrement buttons.
Soft Start Control Period
It can be adjusted from 0 to 100 sec with increment and decrement buttons.