EMKO ESM-9430 Instruction Manual Download Page 32

Parameter can be changed with 
increment and decrement 
buttons

Press Set button to confirm the 
value and access to the next 
parameter.

Unit Selection

For accessing to the other 

menus, press menu changing 

next and back buttons.

TC Input Type Selection

Press Set button to access to 
the next parameter

PINP CONF Menu

When Menu button is pressed, 

technician can access to the 

menu pages.

Operation Screen

Press Menu button for turning 

to the operation screen

Process Input Type Selection

            is             means, input 
type is RTD.

Process Input Type 
Selection

TC input type is selected

PSET

°C

°F

V

V

PO

AO1

AO2

A

AT

ASET1

ASET2

M

SET

P

AT

A/M

°C

°F

V

V

PO

AO1

AO2

A

AT

PSET

ASET1

ASET2

M

SET

P

AT

A/M

PSET

°C

°F

V

V

PO

AO1

AO2

A

AT

ASET1

ASET2

M

SET

P

AT

A/M

PSET

°C

°F

V

V

PO

AO1

AO2

A

AT

ASET1

ASET2

M

SET

P

AT

A/M

PSET

°C

°F

V

V

PO

AO1

AO2

A

AT

ASET1

ASET2

M

SET

P

AT

A/M

PSET

°C

°F

V

V

PO

AO1

AO2

A

AT

ASET1

ASET2

M

SET

P

AT

A/M

32

Summary of Contents for ESM-9430

Page 1: ...e Manual Automatic mode selection for control outputs Bumpless transfer Programmable heating cooling and alarm functions for control outputs digits process PV and Universal process input Configurable...

Page 2: ...explained Operation and Parameters In this section user interface of the device how to access to the parameters description of parameters are explained Also in these sections there are warnings to pre...

Page 3: ...OUTPUT SSR DRIVER OUTPUT CONNECTION 4 2 ALARM OUTPUT 1 RELAY CONNECTION 4 3 PROCESS OUTPUT OR ALARM OUTPUT 2 RELAY CONNECTION 5 DEFINITION OF FRONT PANEL AND ACCESSING TO THE PARAMETERS 5 1 DEFINITIO...

Page 4: ...Voltage Directive 2004 108 EC The Electromagnetic Compatibility Directive has been designed and manufactured to the following specifications EN 61000 6 4 2007 EMC Generic Emission Standard for the Ind...

Page 5: ...Control Plastic Petro Chemistry Textile Automative Machine production industries Alarm Out 1 Relay Output Process Input Power Supply Input Standard 1 1 General Specifications ESM 9430 Standard Standar...

Page 6: ...e then other specifications must be determined Please fill the order code blanks according to your needs Please contact us if your needs are out of the standards 0 21 22 23 25 27 29 31 33 35 37 24 26...

Page 7: ...ch are determined in warranty document and instruction manual performs by the customer completely 1 4 Maintenance Repairs should only be performed by trained and specialized personnel Cut power to the...

Page 8: ...the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented Never attempt to disassemble modify or repair this unit Tampering with the unit may...

Page 9: ...cover Mounting Clamp Front Panel IP65 protection NEMA 4X Panel surface maximum thickness 15mm 0 59 inch Maximum 15mm 0 59 inch 96mm 3 78 inch 48mm 1 89 inch 76mm 2 99 inch 10 5 1 mm 0 41 inch SET A M...

Page 10: ...2 3 Panel Cut Out 10 65 mm 2 56 inch min 92 mm 3 66 inch min 46 mm 1 81 inch min 129 mm 5 08 inch min...

Page 11: ...ting Temperature 0 to 50 C Max Operating Humidity 90 Rh non condensing Altitude Up to 2000m Operating Conditions Forbidden Conditions Corrosive atmosphere Explosive atmosphere Home applications The un...

Page 12: ...xing clamps Be sure that device will not fall while doing the montage c c 1 Loosen the screws 2 Pull mounting clamps from top and bottom fixing sockets 3 Pull the unit through the front side of the pa...

Page 13: ...ualified personnel and technicians should work on this equipment This equipment contains internal circuits with voltage dangerous to human life There is severe danger for human life in the case of una...

Page 14: ...3 24 P N ESM 9430 TC a c CAT II Y 100 240V V 15 10 50 60Hz 6VA 24 V V 15 10 50 60Hz 6VA 24V Z 15 10 6W 24 V Z Max 50mA 0 to 20mA Z 0 to 50mV Z 0 to 10V Z Max 17mA 25V Z Pt 100 ALARM OUT 2 PROCESS OUT...

Page 15: ...9 7 20 8 21 9 22 10 23 N 11 24 L 12 24 V Z Max 50mA 100 to 240 VV 50 60Hz 6VA TC Pt 100 0 to 20mZ 0 to 50mVZ 0 to 10VZ NC NO C 5A 250VV ALARM OUT 2 PROCESS OUT NC NO C 5A 250VV ALARM OUT 1 PROCESS OUT...

Page 16: ...d in order While installing the unit supply voltage range must be controlled and appropriate supply voltage must be applied to the unit Controlling prevents damages in unit and system and possible acc...

Page 17: ...0 meters use 3 wire system 3 wire Pt 100 connection with line compensation Max Line impedance is 10 W 2 wire Pt 100 connection without line compensation 1 1 2 2 3 3 Note 1 Note 2 3 5 1 TC Thermocouple...

Page 18: ...Current Output Loop Powered Transmitter connection by using supply voltage on the device Transmitter connection by using external supply voltage source Transmitter Transmitter External Power Supply No...

Page 19: ...external supply voltage source Transmitter Transmitter External Power Supply Note 1 mV VZ mV VZ PV PV 1 1 2 2 4 4 24 VZ Max 50mA 24 VZ Max 50mA Note 1 External power supply must be selected according...

Page 20: ...nd 1 2000VV For ESM 9430 1 500VV For ESM 9430 2 2000VV 2000VV 2000VV 2000VV 2000VV 2000VV 2000V V Process Output SSR Driver Output Process Output or Alarm Output 2 Relay Analog Inputs Alarm Output 1 R...

Page 21: ...ion 4 2 Alarm Output 1 Relay Connection 21 Fuses must be selected according to the applications c Fuses must be selected according to the applications c 12 L N 11 c Max 25 V Z Max 17mA Device Last Con...

Page 22: ...22 4 3 Process Output or Alarm Output 2 Relay Connection Fuses must be selected according to the applications c 15 13 L N c 14 C NC NO Device 5AVT Fuse Last Control Element Contactor Fuse Load...

Page 23: ...Note 1 If increment or decrement button is pressed for 5 seconds continuously increment and decrement number become 10 if increment or decrement button is pressed for 10 seconds continuously incremen...

Page 24: ...ESM 9430 P SET A M AT C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M Process Controller ESM 9430 P SET A M AT C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M Process Controller ESM 9430 P SET A M AT C F V V PO...

Page 25: ...lues For saving Set v a l u e a n d accessing to the other Set values press Set button Alarm 2 Set Screen Alarm 1 Set Screen ASET1 Led flashes ASET2 Led flashes 25 PSET C F V V PO AO1 AO2 A AT M SET P...

Page 26: ...AT PSET ASET1 ASET2 M SET Proportional Band C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET Integral Time C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET Derivative Time C F V V PO AO1 AO2 A AT PSET ASE...

Page 27: ...pe Set scale High Limit C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET Process Output Control C F V V PO A...

Page 28: ...Screen Technician can access to the former menu by pressing menu changing back button When P button is pressed Technician Menu Entering screen is shown Technician Menu Entering Screen Enter password...

Page 29: ...n can access to the following menu by pressing menu changing next button Technician can access to the former menu by pressing menu changing back button Technician can access to the former menu by pres...

Page 30: ...peration screen By pressing SET button technician can access to the menu page and all parameters in this menu page Technician can access to the former menu by pressing menu changing back button Techni...

Page 31: ...ian Password Entering Screen is shown Enter password with increment and decrement buttons Technician Password Run List Menu Selection of operation form If password is not 0 Technician Password Enterin...

Page 32: ...can access to the menu pages Operation Screen Press Menu button for turning to the operation screen Process Input Type Selection is means input type is RTD Process Input Type Selection TC input type i...

Page 33: ...nual Open Loop Control and there is an output with ON OFF control form then output value can be adjusted or with decrement and increment buttons If operation form is Manual output value is shown on bo...

Page 34: ...ASET2 M SET P AT A M C F V V PO AO1 AO2 A AT PSET ASET1 ASET2 M SET P AT A M PSET C F V V PO AO1 AO2 A AT ASET2 M SET P AT A M ASET1 PSET C F V V PO AO1 AO2 A AT M SET P AT A M ASET1 ASET2 C F V V PO...

Page 35: ...When P button is pressed Technician Menu Entering screen is shown If password is not 0 Technician Password Entering Screen is shown When screen is shown technician parameters can be seen by pressing...

Page 36: ...on parameters of process input Technician can access to the following menu by pressing menu changing next button Technician can access to the former menu by pressing menu changing back button Technici...

Page 37: ...sed technician can access to the menu pages Operation Screen Press Menu button to turn to the operation screen Integral Time Derivative Time PSET C F V V PO AO1 AO2 A AT ASET1 ASET2 M SET P AT A M PSE...

Page 38: ...hnician Menu Entering Screen When P button is pressed Technician Menu Entering screen is shown When Set button is pressed Technician Password Entering Screen is shown Enter password with increment and...

Page 39: ...Input Calibration Type Selection Decimal Point Position Technician can access to the former menu by pressing menu changing back button For accessing to parameter parameter must be If it is not change...

Page 40: ...ameter PINP CONF Menu When Menu button is pressed technician can access to the menu pages Operation Screen Press Menu button to turn to the operation screen Maximum value for selectable dual point cal...

Page 41: ...le Set value for alarm output 2 It is accessible if parameter is For changing Alarm Output 1 and Alarm Output 2 Set values Alarm Set Values protection parameter must be Please refer to the Section 6 2...

Page 42: ...ons in Auto Tune selection which explained below If any of the conditions is realized it performs the Auto Tune operation AUTOMATIC TUNE SELECTION i Device does not do Limit Cycle Tuning operation or...

Page 43: ...n can not be completed in 8 hours 3 If user adjusts parameter or 4 If user adjusts parameter 5 If process set value is changed while Tune operation is being performed 6 While Tune operation is being p...

Page 44: ...menu Select tune selection parameter in run List menu or and turn to operation screen Power off the device Wait system to be in first conditions For example Decrease of the temperature to ambient tem...

Page 45: ...operation is canceled Process Value Time 100 Process Output Stun Start Value Process Set Value Start Value Start Value Set 2 PID coefficients were determined Process Value Time 100 Process Output Stun...

Page 46: ...at Cool Cool Heat 9 While Tune operation is being performed if control form is changed as ON OFF when it is PID If control form is changed as PID when it is ON OFF the Tune operation is started again...

Page 47: ...ual control to automatic control New control output that is measured in automatic control is applied to process output Last output value is taken output value of manual control and manual control cont...

Page 48: ...or 328 F 1652 F J 199 9 C 900 0 C or 199 9 F 999 9 F K 200 C 1300 C or 328 F 2372 F K 199 9 C 999 9 C or 199 9 F 999 9 F R 0 C 1700 C or 32 F 3092 F R 0 0 C 999 9 C or 32 0 F 999 9 F S 0 C 1700 C or 3...

Page 49: ...ion for displays It is active if oltage Current input is selected ZV It is active when oltage Current input is selected It determines calibration type ZV It defines minimum value for selectable dual p...

Page 50: ...erating scale It can be changed according to input type and scale of the process Display offset for process value It can be adjusted 10 to 10 of scale The defined value is added to process value Defin...

Page 51: ...es not run When tune operation stops if this parameter is 0 this parameter can not be changed because of derivative control part does not run OUTPUT ON OUTPUT PERIOD OUTPUT PERIOD Relay Output Output...

Page 52: ...calculates the output value less than this parameter heating or cooling output is active minimum for OLLparameter It is of maximum output Even as a result of the PID calculation device calculates the...

Page 53: ...C C or C shifting of the proportional band is shown below Note Point position changes according to process input type and scale unit changes according to the selection in parameter Scale High Point Ma...

Page 54: ...process value 54 FOR HEATING PID 0 0 100 0 FOR COOLING PID 100 0 0 0 This parameter is added to Output which is calculated at the end of the PID PID OUTPUT OFFSET OUTPUT OFFSET RELATED TO PID SET FOR...

Page 55: ...es according to process input type and scale unit changes according to the selection in parameter PROPORTIONALBAND SHIFTING SCALE HIGH POINT 2 SCALE LOW POINT 2 If heating cooling or only cooling func...

Page 56: ...ing Set Value Soft Start Set value It can be adjusted from 0 to 9999 with increment and decrement buttons When the device power on if the Soft start set value different from 0 and temperature value is...

Page 57: ...F operation this time must be passed for the output to be energised again It can be adjusted from 0 0 to 100 0 seconds It is active if ON OFF control is selected Heating ON OFF control algorithm Cooli...

Page 58: ...ocess Value HYS ON OFF Alarm Set Alarm Output Process Value HYS ON OFF Alarm Set Alarm Output Process Value Output is active when the process value is out of the band which is defined with minimum val...

Page 59: ...on of Alarm Output 1 is alarm output Alarm Status Alarm Output On Delay OFF Delay HYS Process Set Alarm Set HYS ON OFF Process Set Process Set Alarm Set Alarm Output Process Value HYS ON OFF Process S...

Page 60: ...t Process Value It determines logic output function for Alarm Output 2 Alarm output Sensor break alarm output Manual Automatic data output Output is active when the process value is out of the band wh...

Page 61: ...larm Output 2 It can be adjusted from 0000 to 9998 seconds When the value is greater than 9998 is seen on the screen It means alarm latching output is selected It is active if logic output function of...

Page 62: ...tton in Main Operation screen Limit Cycle Tuning operation can not be active or inactive withAT AutoTune Button in Main Operation screen Maximum value for process set and alarm set values It is named...

Page 63: ...chnician parameters 1 If technician does not enter password correctly It turns to operation screen without entering to operator parameters 2 When in top display and in bottom display if technician pre...

Page 64: ...ter than maximum value of operating scale value on the top display starts to blink 3 If value on top display blinks If analogue input value is greater than maximum value of operating scale top display...

Page 65: ...ront IP20 at rear Weight Approximately 0 21 Kg Environmental Ratings Standard indoor at an altitude of less than 2000 meters with none condensing humidity o o o o Storage Operating Temperature 40 C to...

Page 66: ...tors AT Auto Tune M Manual Mode A Automatic Mode PSET Process Set value ASET1 Alarm 1Set value ASET2 Alarm 2 Set value PO Process Output AO1 Alarm Output 1 AO2 Alarm Output 2 C F V unit leds W 100000...

Reviews: