PID -Temperature Protection Parameter
( Default = )
When PID operation is performed, the heating output is switched off if the
temperature value goes above the value defined by . When the value is 0 or
0.0, if the value decrease button is pressed, appears and this function is
disabled.
From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C) ,From 1 to 18°F for
NTC,PTC ,PT-100 (32°F, 212°F),From 0.1 to 10.0°C for NTC, PTC, PT-100
(0.0°C,100.0°C), From 0.1 to 18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F) ,From
1 to 10°C for ProNem Mini PMI-P (-20°C, 80°C) ,From 1 to 18°F for ProNem Mini
PMI-P (-4°F,176°F), From 0.1 to 10.0°C for ProNem Mini PMI-P (-20.0°C,80.0°C),
From 0.1 to 18.0°F for ProNem Mini PMI-P (-4.0°F,176.0°F).
5.1 Programming Mode Parameter List
9
Temperature Control Selection Parameter On/Off or PID ( Default = 0 )
On - Off selected.
PID selected.
PID - Proportional Control Parameter
( Default =1.0 )
This parameter value can be adjusted form 0.1 to 100.0
PID - Integral Parameter
( Default = 300 )
This parameter value can be adjusted form 0 to 3600.
PID - Derivative Parameter
( Default = 60 )
This parameter value can be adjusted form 0 to 999.9
PID -Period Time Parameter
( Default = 1 )
This parameter value can be adjusted form 1 to 150 second.
Note: If this parameter is select 0, PID parameters ( , , , , ) will be not observed.
If this parameter select 1, parameter will be not observed.
Self Tune (Step Response Tuning)
Selection Parameter ( Default =
)
Device does not do (
) operation.
Step Response Tuning
Device does operation.
0..10V
veya 0..20mA
Z
Z
2..10V
veya 4..20mA
Z
Z
Temperature Sensor Scale Selection Parameter ( Default = 0 )
(1)
(2)
(2)
(1)
Analogue (T
input range is determined with this parameter.
emperature)
Temperature
or
or
Sensor Scale Low Limit Parameter : ( Default = 0 )
It can be adjusted from -1999 to ( -1). At this value analogue input becomes;
If =0, according to the device type 0V
0mA
If =1, according to the device type 2V
4mA
Z
Z
Z
Z
(1)
(2)
(1)
(2)
Temperature
or
Sensor Scale High Limit Parameter : ( Default = 100 )
It can be adjusted from ( +1) to 9999. At this value analogue input becomes;
According to the device type10V
20mA
Z
Z
(1)
(2)
Note : ,
parameters are shown, if the Temperature sensor analogue input type is selected .
Note :
, and
parameters are shown, if the Temperature sensor
input type
( 0/2..10V or 0/4..20mA ) is selected.
analogue