11
Maximum Humidity Set Value Parameter (Default = Maximum Value of Device Scale)
This parameter value can be
adjusted from minimum humidity set value parameter to maximum value of the
device scale.
Humidity set value can not be greater than this value.
Minimum Humidity Set Value Parameter (Default = Minimum Value of Device Scale)
set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum
set value parameter
Humidity
Humidity
Humidity Sensor Offset Parameter ( Default = 0.0 )
From -10 to 10 for Humidity Sensor (0%RH, 100%RH)
From -10.0 to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
Humidity Decrease Amount Parameter for Door Opened Control ( Default = )
To detect that the door is opened, the humidity must be reduced in the amount defined by
the parameter in the time defined by the parameter. From -5 to 20 for
Humidity Sensor (0%RH, 100%RH) From 5.0 to 20.0 for Humidity Sensor
(0.0%RH,100.0%RH)
If the value decrease button is pressed while the parameter value
is 5 or 5.0, is displayed and this function is disabled and the parameters and
are not observed.
Humidity Decrease Amount Control Time Parameter for Door Opened Control
( Default = 20)
To detect that the door is opened, the humidity must be reduced in the amount defined
by the parameter in the time defined by the parameter.
Off Time of Humidity Output Parameter for Door Opened Control ( Default = 60 )
When it is detected that the door is opened, the humidity output is switched off for the time
defined by the parameter.
This parameter can be between 10 seconds and 999 seconds.
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z
Humidity Sensor Input.
Z
Humidity Sensor Input
.
(1)
(2)
i
Time of Automatic Egg Tray Rotator ( Default = 00:00 )
This parameter value can be adjusted form 00:00 to 99:59 minute/second.
Repeat cycle of Automatic Egg Tray Rotator ( Default = 00:00 )
This parameter value can be adjusted form 00:00 to 24:00 hour/minute.
Alarm Output Function Selection Parameter
( Default = 0 )
Alarm is inactive.
Alarm-Temperature sensor failures.
Alarm-Humidity sensor failures.
Alarm-Temperature or Temperature sensor failures.
Alarm-Humidity or Humidity sensor failures.
Alarm-Temperature sensor failures or Humidity sensor failures.
Alarm-Temperature or Humidity or Temperature sensor failures or Humidity
sensor failures.
Note :
if parameter value is 3 or 6 , , , , , or parameters are
observed.
Note :
if parameter value is 4 or 6 , , , , , or parameters are
observed.