INFLUENCE 1
F.L.O.T/MN.VNT: NON
T.L.O.T/MN.VNT: -25.0
MAX.VENT.COOL : 8%00
F.L.O.T/T.OFF : NON
T.L.O.T/T.OFF : -25.0
F.L.O.T/MN.VNT:
Influence Factor Low Outside Temperature/ Minimum Ventilation set value
(Range: NON, 0.5, 0.75, 1.0, 1.5, 2.0 / Factory Setting: NON).
T.L.O.T/MN.VNT:
Trajectory Factor Low Outside Temperature/ Minimum Ventilation set value
(Range: -50.0 °C - -5.0 °C / Factory Setting: -25.0 °C)
MAX.VENT.COOL:
Maximum Ventilation of Cooling set value
(Range: NON, 0%00 - 8%00 / Factory Setting: 8%00).
F.L.O.T/T.OFF:
Influence Factor Low Outside Temperature/ Temperature Offset set value
(Range: NON, 0.5, 0.75, 1.0, 1.5, 2.0 / Factory Setting: NON).
T.L.O.T/T.OFF:
Trajectory Factor Low Outside Temperature/ Temperature Offset set value
(Range: -50.0 °C - -5.0 °C / Factory Setting: -25.0 °C).
5.4.16.1 INFLUENCE PARAMETERS
5.4.16 INFLUENCES
INFLUENCE 2
T.O.TMP OFFS: NON
T.RH OFFSET : 5.0
NEG PRESSURE: NON
NEG.PRE.TON : 0
NEG.PRE.TOFF: 0
T.O.TMP OFFS:
Influence Factor High Outside on Temperature Offsets set value
(Range: NON, 0.5, 0.75, 1.0, 1.5, 2.0 / Factory Setting: NON).
T.RH OFFSET:
Trajectory Factor High Outside Temperature/ Temperature Offsets set value
(Range: 5.0 °C - 50.0 °C / Factory Setting: 5.0 °C).
NEG PRESSURE:
Negative pressure influence set value
(Range: 5.0 °C - 50.0 °C / Factory Setting: 5.0 °C).
NEG.PRE.TON:
Negative pressure influence Ton delay set value
(Range: 0 sec - 30 sec / Factory Setting: 0 sec).
NEG.PRE.TOFF:
Negative pressure influence Toff delay set value
(Range: 0 sec - 30 sec / Factory Setting: 0 sec).