Isolate the equipment from the electricity supply during mechanical and
electrical maintenance. When this is not possible, the equipment must be in
the “STOP” position.
c
44
Symptom
Check all the wiring of the unit.
Check the
supply. (measure voltage
Z
between pins 10 and 11)
Check the
fuse.
Z
Check engine oil level and pressure.
Check oil pressure switch and wiring.
Check engine temperature and cooling systems.
Check switch and wiring.
Check fuel solenoid and wiring, fuel and battery.
Reset the
and restart the engine.
EAOM-72F
Check solenoid transistor output activated,
(Fuel Solenoid if selected)
Check the signals that the
is using to determine if the
EAOM-72F
engine has started. Refer to the engine manual.
Check wiring to starter solenoid.
Check battery supply.
Check battery supply is present on the Start output (Pin9) of the
EAOM-72F.
Unit is inoperative.
Starter motor
Inoperative.
Possible Remedy
Low oil pressure fault
after engine has started
Failed to start fault.
Engine failed to start
after Number of Starting
Attempts (P26)
High engine
temperature fault after
engine has started