Definition of Parameter
No
Min
Default
Unit
Max
Configurable Output-2
P41
0
16
0
0 - Alarm out
1 - Engine running
2 - Load permit
3 - Preheat
4 - Over speed
6 - Low fuel level
9 - Maintenance due
10 - Failed to start
11 - Over / under speed
12 - Voltage failure
8 - Low oil pressure
13 - Charging failure
14 - Low battery value
15 - High battery voltage
5 - Over current
7 - High temperature
16 - Weak battery
P42 Oil Pressure Switch / Sender Selection
0
0-Switch
1-Sender
Pressure Lower Limit
P43
0.0
99.9
42.6
Pressure Configuration
P44
0
2
1
0 - Disable the analog input
1 - Pre-alarm
2 - Shut down
Temperature Upper Limit
P45
0
300
176
Temperature Configuration
P46
0
2
1
0 - Disable the analog input
1 - Pre-alarm
2 - Shut down
Level Lower Limit
P47
0
300
75
Level Configuration
P48
0
2
1
0 - Disable the analog input
1 - Pre-alarm
2 - Shut down
Operator Password
P49
0
9990
0
Technician Password
P50
0
9990
0
27