3.4 Connection of Device Supply Voltage Input
16
c
c
c
100 - 240 V
(-15%;+10%) 50/60 Hz
V
24V
(-15%;+10%) 50/60Hz
V
11
N
L
12
Note-1
Y
11
L
12
Y
c
or 24V
(-15%;+10%)
Z
c
a
a
External
Fuse
(1 A
T)
V
External
Fuse
(24V
: 1 A
T)
(24V
: 1 A
T)
V
V
Z
Z
Note-2
N
Fuse
Fuse
Note-3
Note-3
Universal Supply
Voltage Connection
Low Voltage 24 V
Supply Voltage Input
W
Supply Voltage
Power
Supply
Switch
Power
Supply
Switch
Note-1
Supply Voltage
Note-1 :
Note-2 : “L”
N”
There is an internal 33R
fusible flameproof resistor in 100-240 V
50/60Hz supply
voltage input
There is an internal 4R7
fusible flameproof resistor in 24V
50/60Hz , 24V
supply voltage
input
is ( + ) ,”
is ( - ) for 24V
supply voltage
W
W
V
V
Z
Z
Note-3 :
External fuse is recommended.
Make sure that the power supply voltage is the same indicated on the
instrument.
Switch on the power supply only after that all the electrical connections have
been completed.
Supply voltage range must be determined in order. While installing the unit,
supply voltage range must be controlled and appropriate supply voltage must
be applied to the unit. Controlling prevents damages in unit and system and
possible accidents as a result of incorrect supply voltage.
There is no power supply switch on the device. So a power supply switch must
be added to the supply voltage input. In accordance with the safety regulations,
the power supply switch shall bring the identification of the relevant
instrument.Power supply switch shall be easily accessible by the user.
Power switch must be two poled for seperating phase and neutral. On/Off
condition of power switch is very important in electrical connection. On/Off
condition of power switch must be signed for preventing the wrong connection.
If an external fuse is used, it must be on phase connection in
supply input.
If an external fuse is used, it must be on (+) line connection in
supply input.
V
Z
The instrument is protected with an internal fuse (Please refer to Note1 for
information). In case of failure it is suggested to return the instrument to the
manufacturer for repair.