background image

The Right Fit For Comfort

www.retroaire.com

4

!  

!  

All field wiring must be done in accordance to NEC and 

local codes. Check the unit rating plate for circuit ampacity 

and breaker or fuse size. Use only HACR type breakers. 

Select the proper wire for the ampacity rating. If a plug and 

receptacle are used check the proper fit.

The unit is wired for 230V primary voltage from 

the factory. The transformer must be rewired by the 

installer if the jobsite voltage is 208V.

Each  vertical  stack  unit  is  equipped  for  a  24V  wall 

thermostat  connection.  Units  are  shipped  with  a  twenty 

foot plenum rated thermostat wire utilizing a quick connect 

plug to the unit.

STANDARD CONTROLS AND COMPONENTS

• Cooling or heat pump chassis w/high efficiency rotary 

or reciprocating type compressor

• Indoor/outdoor mounting anodized outdoor louver for 

field installation (optional colors available)

•  Manual  fresh  air  damper  (located  on  service  panel 

below evaporator coil)

• Front mounted control box (unless otherwise specified)

• Microprocessor control board

- Fan purge: Fan remains on for 60 seconds after 

heat/cool call is dropped (“Auto” mode only)

- Universal control board: circuit board can be used 

in either a straight cool electric, hydronic heat, or 

cooling/heat pump application.

- Anti-short cycle compressor protection

- Random start timer: prevents multiple units from 

simultaneous start-ups

-  Freeze  protection:  prevents  evaporator  freeze 

ups

- Low ambient lockout

- Test operation: allows ease of testing after instal-

lation (all timers are eliminated)

- Compatible with fossil fuel, electric heat, mercury 

or electronic thermostats

• Temperature sensitive drain pan valve for heating con-

densate disposal (VPHP only)

• Wall sleeve

OPTIONAL CONTROLS AND COMPONENTS

• Hydronic heat coil

• Electric heat coil

• Painted outdoor air louver 

• Wall thermostat (digital or mercury bulb)

• Power disconnect

• EMS management relay

• Casters (for easy maneuverability )

• Return air access panel (standard white or custom 

colors available)

PRODUCT DESCRIPTION

The VPAC/VPHP Single Package Vertical Air Condi-

tioner (SPVAC) and Heat Pump (SPVHP) creates new op-

tions in layout and space utilization. The VPAC/VPHP offers 

low cost operation and quiet, comfortable air distribution, 

especially  when  used  in  multi-room  suites,  apartments, 

healthcare facilities, and homes.

Framed into a concealed closet enclosure for low op-

erating sound levels, the VPAC/VPHP’s vertical discharge 

vent allows ducting to the top of the room(s) for superior air 

circulation and distribution. Multiple air supply grilles can 

distribute air when used with a soffit and intake grilles can 

be located on either of the two sides of the enclosure.

The VPAC/VPHP offers an economic benefit when used 

in a multi-room suite by supplying conditioned air to more 

than one room without the need to install another unit. This 

is also a design advantage since the second room does 

not need an exterior wall for a second unit.  

Each  system  is  supplied  with  a  ready-to-install  wall 

sleeve  and  a  condenser  side  air  louver. The  cabinet  is 

constructed with 20 gauge galvanized steel with a G-90U 

corrosion resistant rating. The unit is designed with service-

ability on three sides (front, left, and right). The insulated top 

discharge evaporator compartment provides quiet ducted, 

conditioned air delivery to other room location(s).  

AIR SYSTEMS

Motors are thermally protected PSC type. Air stream 

surfaces are insulated with 1/4 inch fiberglass or 1/8 inch 

volara. The evaporator fan is a forward curved type directly 

mounted to the motor shaft. The condenser propeller and 

slinger ring (for condensate re-evaporation) utilize a blow-

thru design for improved efficiency.

IMPORTANT: 

Consult  the  factory  if  an  internal 

condensate drain system will be used. The standard 

VPAC/VPHP is designed to evaporate condensate by 

slinging it onto the warm condenser coil.

ELECTRICAL WIRING

WARNING

Before accessing the control compartment, disconnect 

power to the unit. Failure to do so could result in serious 

injury or electrical shock.

ELECTRICAL WIRING 

Continued

Summary of Contents for VPAC

Page 1: ...00 Certified Company VPAC VPHP SINGLE PACKAGE VERTICAL AIR CONDITIONER HEAT PUMP FOR NEW CONSTRUCTION ONLY Straight Cool Heat Pump Nominal Capacities 9 000 12 000 15 000 17 000 19 000 24 000 Btuh VPAC VPHP Enviromaster International LLC 5780 Success Dr Rome NY 13440 Email info retroaire com ...

Page 2: ... stated on the rating plate Have proper over current protection i e time delay fuse HACR Breaker as listed on the Rating Plate Failure to follow these instructions can result in a fire explosion or electrical shock causing property damage personal injury or death This manual is intended as an aid to qualified service personnel for proper installation operation and maintenance of the VPAC VPHP Packag...

Page 3: ...allation Instructions 5 9 Sequence of Operation 10 12 Cleaning and Maintenance 12 Troubleshooting 12 Specifications and Dimensions 13 14 Warranty 15 INSTALLER RESPONSIBILITIES This manual has been prepared to acquaint you with the installation operation and maintenance of this VPAC VPHP PTAC and to provide important safety information in these areas We urge you to read all of the instructions thoro...

Page 4: ...ess panel standard white or custom colors available PRODUCT DESCRIPTION The VPAC VPHP Single Package Vertical Air Condi tioner SPVAC and Heat Pump SPVHP creates new op tions in layout and space utilization The VPAC VPHP offers low cost operation and quiet comfortable air distribution especially when used in multi room suites apartments healthcare facilities and homes Framed into a concealed closet...

Page 5: ... position necessary for installation Figure 1 INSTALLATION FOR NEW CONSTRUCTION EXPLODED VIEW OF TYPICAL INSTALLATION Rear View of Door Filter Slide On Back Access Panel Optional Evaporator Coil Manual Fresh Air Door External line cord min 48 located at bottom right for front and right hand controls or bottom left for left hand controls Minimum overall wall thickness must be at least 5 for straigh...

Page 6: ...VPHP WALL SLEEVE ASSEMBLY CROSS SECTION OF TYPICAL WALL Wall Sleeve Outdoor Louver Interior Wall Lag Holes 4 On Each Side Wall Sleeve Depth Overall Wall Thickness 1 25 Louver Depth 1 2 x 1 2 Foam Gasket Overall Wall Thickness DETERMINING WALL SLEEVE DEPTH Figure 2 Weather Angle Position INSULATION WEATHER ANGLES Back Panel Mounting Holes Install supplied 1 2 x 1 2 foam insulation along top and sid...

Page 7: ...ot equipped with a drain stub a minimal amount of condensate will during the heating cycle run out the wall sleeve onto the drip edge and away from the building when the drain pan valve opens During the cooling cycle condensate will be funneled to an area near the condensing fan and picked up by the slinger ring The condensate will be slung against the hot condenser coil to evaporate Any excess co...

Page 8: ...t or front aligned matching the control section alignment of the unit on which it is to be installed 1 The coil package is centered on top of the VPAC VPHP chassis Make sure it is centered over the fan discharge and that the piping package is in the correct position 2 Find the two Z brackets used to clamp the hydronic enclosure to the chassis top Mount these brackets to the chassis top using the h...

Page 9: ...se as a temporary heating cooling source during construction MANUAL FRESH AIR DAMPER The fresh air manual damper allows the user to move fresh air into the space to be conditioned The damper handle is located below the evaporator coil on the service panel RETURN AIR ACCESS PANEL NOTE Available with solid doors if separate intake is used B C A Frame Assembly Lag Holes 1 5 Rear View Of Door G NOTE A...

Page 10: ...e adjustment screw is tampered with it will be necessary to reset the freeze stat To set the freeze stat you will need a medium flat bladed screwdriver Turn the adjusting screw counter clockwise until it stops Then slowly turn the ad justing screw clockwise approximatly 1 8 turn until a click is detected The freeze stat is now set CHOOSING A THERMOSTAT Enviromaster International offers a thermostat...

Page 11: ...valve that will open when outdoor temperatures fall below 50 F This keeps the base pan free of condensate water where it may otherwise freeze during colder outdoor temperatures As part of its normal operation the unit will produce condensate and collect it in the base pan of the unit There it will be picked up by the condenser fan slinger ring and deposited onto the condenser coil During the cooli...

Page 12: ...lies Some units may require a drop of light oil to motors and or bearing assemblies look for oil cups Check setscrews and motor mounting hardware making sure these are tight 6 Centrifugal fan blades and blower cage assemblies must be clean to operate efficiently Brush and or vacuum as necessary 7 Inspect both indoor and outdoor coils Use a fin comb to straighten out any damaged fins These coils must...

Page 13: ...5 60 1 0 70 0 125 4 25 26 0 67 0 08 5 62 240 6 7 15 H WIRE 15 208 230 60 1 0 72 0 125 6 40 35 0 80 0 07 7 92 197 9 6 15 6 15P 265 60 1 0 70 0 125 5 40 32 0 67 0 08 6 77 240 8 2 15 H WIRE 17 208 230 60 1 1 20 0 250 7 40 48 1 00 0 15 9 60 197 11 5 15 6 15P 265 60 1 1 30 0 250 6 50 44 0 67 0 08 8 50 240 10 1 15 H WIRE 19 208 230 60 1 1 00 0 250 7 40 48 1 00 0 15 9 40 197 11 3 15 6 15P 24 208 230 60 1...

Page 14: ... 15 7 17 2 21 2 25 6 30P 230 4000 13700 17 4 18 9 23 2 25 6 30P 265 5310 18200 20 0 21 5 26 5 30 H WIRE 5 208 4089 14000 19 7 21 2 26 1 30 6 30P 230 5000 17100 21 7 23 2 28 7 30 6 30P 7 208 5725 19600 27 5 29 0 35 9 40 H WIRE 230 7000 23900 30 4 31 9 39 5 40 H WIRE 265 6635 22700 25 0 26 5 32 8 35 H WIRE 277 7250 24800 26 2 27 7 34 2 35 H WIRE 10 208 8178 28000 39 3 40 8 50 6 60 H WIRE 230 10000 3...

Page 15: ...nditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequence of any misapplication abuse improper servicing unauthorized alteration or improper operation Damage as a result of floods winds fires lightening accidents corrosive atmosphere or other conditions beyond the control of EMI Parts not supplied...

Page 16: ......

Reviews: