background image

11

Made in Rome, New York, USA

VPAC/VPHP

!  

!  

HEAT PUMP COOLING OPERATION 

(VPHP ONLY)

Cooling operation in a heat pump unit is described in 

“Cooling Operation” above. The unit is equipped with a re-

versing valve that is energized for cooling and de-energized 

in heating mode.

HEAT PUMP HEATING OPERATION

 (VPHP ONLY)

Heat pump units are “Limited Range” equipped with 

back-up electric resistance heat. Limited range heat pumps 

are designed to operate when outdoor temperatures are 

between 75°F and 40°F and with a maximum indoor tem-

perature of 80°F. When the outdoor temperature falls below 

approximately 40°F the unit will switch from heat pump to 

electric resistance heat. Electric heat will then remain as the 

heat source until the outdoor temperatures rise above 50°F.  

The VPHP is a single-stage heating unit. The electric heat 

and heat pump will not operate simultaneously. 

To operate the unit in heating mode, it must first be 

connected to an appropriate heat pump thermostat. (See 

“choosing  a  thermostat”).  Select  heat  on  the  thermostat 

system switch. Then, adjust the set-point temperature above 

the  room  temperature. The  compressor  and  fan  motors 

will start and heating will begin. If the outdoor temperature 

is  below  approximately  40°F  the  heat  pump  system  will 

not operate. Electric heat will then take over the heating 

demand.  Heating  will  continue  so  long  as  the  set-point 

temperature remains above the room temperature. Place 

the set-point temperature below the room temperature. The 

heating mode will cease and the indoor fan will remain on 

for an additional sixty seconds.

IMPORTANT: 

The start of the compressor will not take 

place until the anti-short/random start time period has 

elapsed.

EMERGENCY HEAT 

(VPHP ONLY)

WARNING

Before accessing the control compartment, disconnect 

power to the unit. Failure to do so could result in serious 

injury or electrical shock.

Should the heat pump system fail, it is possible to force 

the control board into electric heat mode. This is a tempo-

rary solution until the heat pump system can be repaired. 

Locate the circuit board in the control section of the unit. 

Locate the terminals where the outdoor sensor connects 

to the circuit board. Using a small needle nose type pliers, 

disconnect one side of the sensor from the circuit board. 

This will appear to the circuit board as an outdoor coil freeze 

condition, thereby energizing the electric resistance heater 

on the call for heat.

THERMOSTATIC DRAIN PAN VALVE

 (VPHP ONLY)

Heat  pump  units  are  equipped  with  a  thermostatic 

drain valve that will open when outdoor temperatures fall 

below 50°F. This keeps the base pan free of condensate 

water where it may otherwise freeze during colder outdoor 

temperatures. As part of its normal operation, the unit will 

produce condensate and collect it in the base pan of the unit. 

There it will be picked up by the condenser fan slinger ring 

and deposited onto the condenser coil. During the cooling 

season, this improves the unit’s efficiency by maintaining 

adequate refrigeration system pressures.

CHANGEOVER THERMOSTAT

 (VPHP Only)

This feature has been replaced by a circuit board how-

ever is still used on some units. The changeover thermostat 

monitors outdoor temperature for efficient heat pump opera-

tion. In heating, the thermostat will determine weather to 

use heat pump or electric resistance heat. When outdoor 

temperatures fall below approximately 35°F, the changeover 

thermostat (COT) will switch from heat pump operation to 

electric resistance heat. Electric heat will remain the primary 

heat source until outdoor temperature rises above 50°F. The 

COT is factory pre-set and should never need adjusting. If 

the adjustment screw is tampered with it will be necessary 

to reset the freeze-stat. To set the freeze stat you will need 

a medium flat bladed screwdriver. Turn the adjusting screw 

counter-clockwise until it stops. Then slowly turn the adjust-

ing screw clockwise approximately 1/8 turn until a click is 

detected. The freeze stat is now set.  

ANTI-SHORT CYCLE TIMER RANDOM START

This feature will prevent compressor short cycling and 

also prevent multiple units in a single facility from simultane-

ously starting following a power outage. This delay on break 

feature ensures that the compressor remains off between 

cycles until the three-minute time delay period has elapsed, 

allowing system pressures to equalize before restarting.

The random start feature, initiated after a power failure, 

will add a random time delay (between 5-120 seconds) to 

the  three-minute  anti  short  cycle  time  following  a  power 

outage. This will stagger the starting of multiple units in a 

single facility allowing a building to slowly go back on line 

when power is restored.

INDOOR COIL FREEZE PROTECTION

This feature will prevent the indoor coil from freeze up in 

the cooling mode. Indoor coil freeze up can occur due to a 

dirty air filter, low refrigerant charge or low room or outdoor 

temperatures. This in turn can cause compressor damage. 

Should a freeze condition be detected, the compressor and 

condenser fan will be switched off for a minimum of three 

minutes and until the freeze condition is satisfied. During 

this time the indoor fan will continue to run to aid in the 

defrost process.

SEQUENCE OF OPERATION

Summary of Contents for VPAC

Page 1: ...00 Certified Company VPAC VPHP SINGLE PACKAGE VERTICAL AIR CONDITIONER HEAT PUMP FOR NEW CONSTRUCTION ONLY Straight Cool Heat Pump Nominal Capacities 9 000 12 000 15 000 17 000 19 000 24 000 Btuh VPAC VPHP Enviromaster International LLC 5780 Success Dr Rome NY 13440 Email info retroaire com ...

Page 2: ... stated on the rating plate Have proper over current protection i e time delay fuse HACR Breaker as listed on the Rating Plate Failure to follow these instructions can result in a fire explosion or electrical shock causing property damage personal injury or death This manual is intended as an aid to qualified service personnel for proper installation operation and maintenance of the VPAC VPHP Packag...

Page 3: ...allation Instructions 5 9 Sequence of Operation 10 12 Cleaning and Maintenance 12 Troubleshooting 12 Specifications and Dimensions 13 14 Warranty 15 INSTALLER RESPONSIBILITIES This manual has been prepared to acquaint you with the installation operation and maintenance of this VPAC VPHP PTAC and to provide important safety information in these areas We urge you to read all of the instructions thoro...

Page 4: ...ess panel standard white or custom colors available PRODUCT DESCRIPTION The VPAC VPHP Single Package Vertical Air Condi tioner SPVAC and Heat Pump SPVHP creates new op tions in layout and space utilization The VPAC VPHP offers low cost operation and quiet comfortable air distribution especially when used in multi room suites apartments healthcare facilities and homes Framed into a concealed closet...

Page 5: ... position necessary for installation Figure 1 INSTALLATION FOR NEW CONSTRUCTION EXPLODED VIEW OF TYPICAL INSTALLATION Rear View of Door Filter Slide On Back Access Panel Optional Evaporator Coil Manual Fresh Air Door External line cord min 48 located at bottom right for front and right hand controls or bottom left for left hand controls Minimum overall wall thickness must be at least 5 for straigh...

Page 6: ...VPHP WALL SLEEVE ASSEMBLY CROSS SECTION OF TYPICAL WALL Wall Sleeve Outdoor Louver Interior Wall Lag Holes 4 On Each Side Wall Sleeve Depth Overall Wall Thickness 1 25 Louver Depth 1 2 x 1 2 Foam Gasket Overall Wall Thickness DETERMINING WALL SLEEVE DEPTH Figure 2 Weather Angle Position INSULATION WEATHER ANGLES Back Panel Mounting Holes Install supplied 1 2 x 1 2 foam insulation along top and sid...

Page 7: ...ot equipped with a drain stub a minimal amount of condensate will during the heating cycle run out the wall sleeve onto the drip edge and away from the building when the drain pan valve opens During the cooling cycle condensate will be funneled to an area near the condensing fan and picked up by the slinger ring The condensate will be slung against the hot condenser coil to evaporate Any excess co...

Page 8: ...t or front aligned matching the control section alignment of the unit on which it is to be installed 1 The coil package is centered on top of the VPAC VPHP chassis Make sure it is centered over the fan discharge and that the piping package is in the correct position 2 Find the two Z brackets used to clamp the hydronic enclosure to the chassis top Mount these brackets to the chassis top using the h...

Page 9: ...se as a temporary heating cooling source during construction MANUAL FRESH AIR DAMPER The fresh air manual damper allows the user to move fresh air into the space to be conditioned The damper handle is located below the evaporator coil on the service panel RETURN AIR ACCESS PANEL NOTE Available with solid doors if separate intake is used B C A Frame Assembly Lag Holes 1 5 Rear View Of Door G NOTE A...

Page 10: ...e adjustment screw is tampered with it will be necessary to reset the freeze stat To set the freeze stat you will need a medium flat bladed screwdriver Turn the adjusting screw counter clockwise until it stops Then slowly turn the ad justing screw clockwise approximatly 1 8 turn until a click is detected The freeze stat is now set CHOOSING A THERMOSTAT Enviromaster International offers a thermostat...

Page 11: ...valve that will open when outdoor temperatures fall below 50 F This keeps the base pan free of condensate water where it may otherwise freeze during colder outdoor temperatures As part of its normal operation the unit will produce condensate and collect it in the base pan of the unit There it will be picked up by the condenser fan slinger ring and deposited onto the condenser coil During the cooli...

Page 12: ...lies Some units may require a drop of light oil to motors and or bearing assemblies look for oil cups Check setscrews and motor mounting hardware making sure these are tight 6 Centrifugal fan blades and blower cage assemblies must be clean to operate efficiently Brush and or vacuum as necessary 7 Inspect both indoor and outdoor coils Use a fin comb to straighten out any damaged fins These coils must...

Page 13: ...5 60 1 0 70 0 125 4 25 26 0 67 0 08 5 62 240 6 7 15 H WIRE 15 208 230 60 1 0 72 0 125 6 40 35 0 80 0 07 7 92 197 9 6 15 6 15P 265 60 1 0 70 0 125 5 40 32 0 67 0 08 6 77 240 8 2 15 H WIRE 17 208 230 60 1 1 20 0 250 7 40 48 1 00 0 15 9 60 197 11 5 15 6 15P 265 60 1 1 30 0 250 6 50 44 0 67 0 08 8 50 240 10 1 15 H WIRE 19 208 230 60 1 1 00 0 250 7 40 48 1 00 0 15 9 40 197 11 3 15 6 15P 24 208 230 60 1...

Page 14: ... 15 7 17 2 21 2 25 6 30P 230 4000 13700 17 4 18 9 23 2 25 6 30P 265 5310 18200 20 0 21 5 26 5 30 H WIRE 5 208 4089 14000 19 7 21 2 26 1 30 6 30P 230 5000 17100 21 7 23 2 28 7 30 6 30P 7 208 5725 19600 27 5 29 0 35 9 40 H WIRE 230 7000 23900 30 4 31 9 39 5 40 H WIRE 265 6635 22700 25 0 26 5 32 8 35 H WIRE 277 7250 24800 26 2 27 7 34 2 35 H WIRE 10 208 8178 28000 39 3 40 8 50 6 60 H WIRE 230 10000 3...

Page 15: ...nditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a consequence of any misapplication abuse improper servicing unauthorized alteration or improper operation Damage as a result of floods winds fires lightening accidents corrosive atmosphere or other conditions beyond the control of EMI Parts not supplied...

Page 16: ......

Reviews: