Multi-zone Heat Pump Condensing Units

MULTI-ZONE CONDENSER SEQUENCE OF OPERATION

When the outdoor temperature falls below 

35°F, compressor operation will cease. At 

that point the unit will switch on the indoor 

units electric heater to assume the heating 

demand, 

(second stage of heat)

.

Note:

 

For full operation the indoor unit 

must have an electric heater.

        

 

(C ) B R N

(W) WHT

(Y) B L K

(O) OR G

(R ) R E D

(G) G R N

(R ) R E D

(R ) R E D

(O) OR G

(O) OR G

(G) G R N

(Yin) B L K

(W) WHT

(Y) YE L

(C ) B R N

(W) WHT

(Y) YE L

(C ) B R N

OPTIONAL WALL T'S TAT

I.D. UNIT

O.D. UNIT

Heat Pump Applications

��

��

WL HA Wall unit

** - E lectric heat option

us e a " C "  terminal

* - S ome thermos tats  do not

 

YEL (Y1)

 

 

O.D. UNIT

 

(C) BRN

 

Y

 

R

 

*

 

C

 

I.D. UNIT

 

BLK (Y)

 

BRN (C)

 

RED (R)

 

(Y) YEL

 

* SOME T"STATS MAY NOT

 

HAVE A "C" TERMINAL

 

GRN (G)

 

(R) RED

 

(W) WHT

 

OPTIONAL

 

W

 

G

 

(O) ORG

 

O

 

WHT (W)

 

INTERCONNECT DIAGRAM

 

CAHB W/ OPTIONAL

 

ELECTRIC HEAT, LOW VOLTAGE

 

OPTIONAL WALL T'S TAT

Refer to the indoor unit for the proper low Volt interconnect wiring.

LOW VOLT INTERCONNECT DIAGRAMS

OPERATION AND MAINTENANCE

The EMI America Series outdoor section is 

the compressor bearing unit of the system. It 

operates at the command of the  indoor sec-

tion or room thermostat. Therefore, the opera-

tion will be described in the manual pertaining 

to the indoor section. The S & T series (S2HA, 

T2HA, T3HA & T4HA) will cease compressor 

operation at 35°F outdoor temperature. If in 

heating mode, the electric heat will take over 

when the compressor ceases operation.
EMI units are designed and constructed for 

reliability and long life with minimal main-

tenance. You  can  assure  peak  operating 

efficiency by regularly inspecting for free air 

passage into and through the coil. If debris 

collect on the air coil, it should be cleaned by 

"back-flushing" with a spray of water or vacu-

uming. 

TURN OFF POWER SUPPLY FIRST.

 

Outdoor units may be cleaned or waxed if 

desired.  Use a non-abrasive car wax.
Panels should remain on the unit at all times. 

Service should be performed by a 

QUALI-

FIED

 service agency only.

GENERAL RECOMMENDATIONS

Do not charge the 

straight cool

 units on 

cold days unless weighing in the charge. 

The 

heat pump

 systems may be charged 

in heat cycle between 35 and 75°F. 

These 

units use a heat cycle TXV and cannot 

be charged to superheat; use weight or 

subcooling method only.

Charging  should  be  done  with  a  dial-a-

charge or weighed in with a scale.

SPECIFIC CHANGES

All EMI products are subject to ongoing de-

velopment programs so design and specifi-

cations may change without notice. Please 
consult the factory for more information.

NOTE:

 For more information, please visit 

our web-site at www.enviromaster.com or 

call 1-800-228-9364.

Summary of Contents for S2HA

Page 1: ...1 1 04 07 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company S2HA Multi Zone S2HA T2HA HE...

Page 2: ......

Page 3: ...the electric supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn of...

Page 4: ...pad or foundation Refrigerant piping Disconnect switch SITE PREPARATION Place the unit on a at concrete surface or pad if on the ground Roof mounting should use a build up platform Piping is through...

Page 5: ...allows for permanent mounting through the feet This is highly recommended due to the vertical design of the unit S2HA UNIT MOUNTING SECTION 5 Insert lag bolts through the holes in the bottom of the un...

Page 6: ...within 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief tting 7 Run wires to the h...

Page 7: ...east 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel 11 Tighten a...

Page 8: ...irements 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating Removethe four screws on the front panel 4 To access wiring diagram a Remove the four...

Page 9: ...wires to the High Volt pigtail in the control box and attach L1 and L2 connections Also run green wire to ground lug T2HA INSTALLATION INSTRUCTIONS 8 Check wiring diagram for the required number of lo...

Page 10: ...Wholesaler or Distributor how ever the trap should be shallow as the 4 elbow con guration Each elbow is approximately 2 equivalent feet One P trap is equal to approximately 8 equivalent feet P TRAP I...

Page 11: ...ing and insert into ttings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap metal to protect the paint 4 Braze tubing into ttings S2C Shown S2HA T2HA REFRIGERAN...

Page 12: ...he Refrig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper system pressures and temperature at different outdoor condi tions Superheat should be used f...

Page 13: ...ning time between charge adjustments for the unit to stabilize The S T series S2HA T2HA T3HA T4HA has manifold access points on each of the service valves for the high and low pressures in cooling mo...

Page 14: ...densing Units MULTI ZONE HEAT PUMP FIELD CHARGING Cooling Cycle 9 000 Btuh Circuit with EMI s WLHA09 or CAHB12 Note Minimum compressor superheat 5 F Cooling Cycle 12 000 Btuh Circuit with EMI s WLHA12...

Page 15: ...ensing Units Cooling Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor superheat 5 F Cooling Cycle 24 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor s...

Page 16: ...nviromaster com 16 Multi zone Heat Pump Condensing Units Heat Cycle 9 000 Btuh Circuit with EMI WLHA09 or CAHB12 Heat Cycle 12 000 Btuh Circuit with EMI WLHA12 or CAHB12 MULTI ZONE HEAT PUMP FIELD CHA...

Page 17: ...romaster com 17 Multi zone Heat Pump Condensing Units MULTI ZONE HEAT PUMP FIELD CHARGING Heat Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Heat Cycle 24 000 Btuh Circuit with EMI s WLHA24 or...

Page 18: ...ines occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gauge 2 M...

Page 19: ...ci c to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evapo...

Page 20: ...located in the indoor unit provides 24V low Volt control power to the condenser outdoor unit This can be mea sured across low Volt terminals R and C Heat pump condensers utilize a reversing valve to p...

Page 21: ...ibed in the manual pertaining to the indoor section The S Tseries S2HA T2HA T3HA T4HA will cease compressor operation at 35 F outdoor temperature If in heating mode the electric heat will take over wh...

Page 22: ...230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compressor...

Page 23: ...600 13 0 80 12 2 16 000 3 3 2200 WLHA12 WLHA12 22 600 13 0 72 11 9 20 000 3 3 9200 WLHA09 WLHA12 20 600 13 0 76 12 0 18 000 3 3 S2HA CAHB SYSTEM PERFORMANCE DATA MODEL COOLING HEATING S2HA Outdoor Ind...

Page 24: ...Lift Liquid Line OD Suction Line OD 9 000 100 35 1 4 1 2 12 000 100 35 1 4 1 2 18 000 100 35 3 8 5 8 24 000 100 35 3 8 3 4 T2HA T3HA AND T4HA 208 230V 60 HERTZ 1 PHASE CAPACITY FAN MTR COMPRESSOR TOTA...

Page 25: ...5 12 1 40500 3 2 CAHB T2HA SYSTEM PERFORMANCE DATA Model Cooling Heating T2HA Outdoor Condenser Indoor Air Handler Btuh SEER SHR EER Btuh COP 8800 CAHB24 CAHB24 36000 13 0 75 12 6 26400 3 1 8400 CAHB2...

Reviews: